No.
Code
Alarm description
80
10078
Circuit A High Discharge Gas Temperature
81
10079
Circuit B High Discharge Gas Temperature
82
10080
Circuit C High Discharge Gas Temperature
83
10081
Circuit A Suction valve closed
84
10082
Circuit B Suction valve closed
85
10083
Circuit C Suction valve closed
86
10087
Circuit A Slide Valve Control Unverifiable
87
10088
Circuit B Slide Valve Control Unverifiable
88
10089
Circuit C Slide Valve Control Unverifiable
89
10090
Cooler Flow Switch Setpoint Configuration
Failure
90
10091
Cooler Flow Switch Failure
91
10100
Electrical Box Fan Failure
92
10097
Water Exchanger Temperature Sensors
Swapped
Maintenance alarms
93
13nnn
Service Maintenance Alert Number
001: Circuit A Loss of charge
002: Circuit B Loss of charge
004: Water loop size warning
005: Air exchanger cleanness warning
006: Cooler pump 1 servicing required
007: Cooler pump 2 servicing required
008: Condenser pump 1 servicing required
010: Water filter servicing required
011: Compressor A oil filter servicing required
012: Compressor B oil filter servicing required
015: Replacement of expansion valve
required on circuit A
016: Replacement of expansion valve
required on circuit B
Software failure
94
55001
Database Module Failure
95
56001
Lenscan Module Failure
Device failure
96
57020
Main EXV stepper motor Failure - cir A
97
57021
Main EXV stepper motor Failure - cir B
98
57022
Main EXV stepper motor Failure - cir C
99
57023
EXV eco stepper motor Failure - cir A
100
57024
EXV eco stepper motor Failure - cir B
101
57025
EXV eco stepper motor Failure - cir C
102
10050
Refrigerant Leakage Detection
Compressor alarms
103
1101
Compressor A Motor temperature too high
104
1102
Compressor A Motor temperature out of
range
Reset type
Manual
Manual
Not applicable to this unit
Manual
Manual
Not applicable to this unit
Manual
Manual
Not applicable to this unit
Manual
Automatic (the first alarm
within the last 24 hours) or
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Not applicable to this unit
Manual
Manual
Not applicable to this unit
Automatic
Manual
Manual
Action taken
Circuit A shuts down
Circuit B shuts down
Circuit A shuts down
Circuit B shuts down
None
None
Unit is not allowed to restart
Compressors and the
evaporator pump are stopped
Unit shuts down
Unit shuts down
None
Unit shuts down
Unit shuts down
Circuit A shuts down
Circuit B shuts down
Circuit A shuts down
Circuit B shuts down
None
Unit shuts down
Unit shuts down
Possible cause
Defective transducer,
max. condensing
temperature setpoint too
low or refrigerant charge
too high
As above
Economizer pressure
transducer defective,
suction valve fault
As above
Defective or incorrectly
wired solenoid valves,
defective current
transformer
As above
Defective flow controller
or wiring error
As above
Electrical box fan
malfunction or fan current
probe malfunction
Leaving water tempera-
ture is higher than entering
water temperature
Preventive maintenance
date has passed;
servicing action required;
contact Carrier Service
Agency
Software problem.
Contact Carrier Service
As above
EXV motor fault
EXV motor fault
Eco EXV motor fault
Eco EXV motor fault
Refrigerant leak or leak
detector defective
Motor/wiring fault
Probe defective or
incorrect wiring
33