Carrier Touch Pilot Manual page 18

For 61xwhze heat pumps
Table of Contents

Advertisement

Run Times Menu – RUNTIME (continued)
No.
Name
10
hr_cpum2
11
hr_hpum1
12
hr_hpum2
*Depends on the selected language (English by default).
Modes Menu – MODES
No.
Name
1
m_delay
2
m_2stpt
3
m_reset
4
m_demlim
5
m_ramp
6
m_pmprot
7
m_pmpper
8
m_night
9
m_slave
10
m_autoc
11
m_lowEwt
12
m_cpmpro
13
m_cpmppr
14
m_ice
15
m_sst_a
16
m_sst_b
17
m_sst_c
18
m_map_a
19
m_map_b
20
m_map_c
21
m_hp_a
22
m_hp_b
23
m_hp_c
*Depends on the selected language (English by default).
Setpoint Menu – SETPOINT
No.
Name
Status
1
csp1
-5 to 32
2
csp2
-5 to 32
3
ice_sp
-29 to 26
4
cramp_sp
0.1 to 11.1
5
hsp1
35 to 85
6
hsp2
35 to 85
7
hramp_sp
0.1 to 11.1
8
cauto_sp
3.9 to 50
9
hauto_sp
0 to 46
10
w_sct_sp
26.7 to 60
11
lim_sp1
0 to 100
12
lim_sp2
0 to 100
13
lim_sp3
0 to 100
*Depends on the selected language (English by default).
18
Status
Unit
-
hour
-
hour
-
hour
Status
Unit
no/yes
-
no/yes
-
no/yes
-
no/yes
-
no/yes
-
no/yes
-
no/yes
-
no/yes
-
no/yes
-
no/yes
-
no/yes
-
no/yes
-
no/yes
-
no/yes
-
no/yes
-
no/yes
-
no/yes
-
no/yes
-
no/yes
-
no/yes
-
no/yes
-
no/yes
-
no/yes
-
Default
Unit
20
°C
20
°C
6.7
°C
0.6
^C
70
°C
70
°C
0.6
^C
23.9
°C
17.8
°C
35
°C
100
%
100
%
100
%
Displayed text*
Cooler Pump #2 Hours
Condenser Pump #1 Hours
Condenser Pump #2 Hours
Displayed text*
Start Up Delay In Effect
Second Setpoint In Use
Reset In Effect
Demand limit active
Ramp Loading Active
Cooler Pump Rotation
Pump Periodic Start
Night Low Noise Active
Master Slave Active
Auto Changeover Active
Heating Low EWT Lockout
Condenser Pump Rotation
Cond Pump Periodic Start
Ice Mode In Effect
Low Suction Circuit A
Low Suction Circuit B
Low Suction Circuit C
Map compressor Circuit A
Map compressor Circuit B
Map compressor Circuit C
High Pres Override Cir A
High Pres Override Cir B
High Pres Override Cir C
Displayed text*
Cooling Setpoint 1
Cooling Setpoint 2
Cooling Ice Setpoint
Cooling Ramp Loading
Heating Setpoint 1
Heating Setpoint 2
Heating Ramp Loading
Cool Changeover Setpt
Heat Changeover Setpt Not applicable to this unit
Water Val Condensing
Stp
Switch Limit Setpoint 1
Switch Limit Setpoint 2
Switch Limit Setpoint 3
Description
Operating hours, evaporator pump 2
Operating hours, condenser pump
Not applicable to this unit
Description
Start-up delay in effect
Second setpoint in use
Setpoint reset active
Demand limit active
Ramp loading active
Evaporator pump rotation
Pump periodic start active
Night low noise active
Master/Slave mode active
Not applicable to this unit
Heating low EWT lockout
Not applicable to this unit
Condenser pump periodic start
Ice storage mode active (EMM option)
Low suction, circuit A
Low suction, circuit B
Not applicable to this unit
Compressor mapping, circuit A
Compressor mapping, circuit B
Not applicable to this unit
High pressure override, circuit A
High pressure override, circuit B
Not applicable to this unit
Description
Cooling setpoint 1 (used during occupied periods)
Cooling setpoint 2 (used during unoccupied periods)
Ice storage setpoint
Cooling ramp loading setpoint (rate at which the water
temperature may change within one minute in Cooling)
Heating setpoint 1 (used during occupied periods)
Heating setpoint 2 (used during unoccupied periods)
Heating ramp loading setpoint (rate at which the water
temperature may change within one minute in Heating)
Not applicable to this unit
Water valve condensing setpoint
Demand limit setpoint 1
Demand limit setpoint 2
Demand limit setpoint 3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents