Carrier Touch Pilot Manual page 31

For 61xwhze heat pumps
Table of Contents

Advertisement

No.
Code
Alarm description
12
15018
Circuit A Condenser Subcooling Liquid
Thermistor
13
15019
Circuit B Condenser Subcooling Liquid
Thermistor
14
15021
Space Temperature Thermistor
15
15024
Circuit A Economizer Gas Thermistor
16
15025
Circuit B Economizer Gas Thermistor
17
15026
Circuit C Economizer Gas Thermistor
Transducer failures
18
12001
Circuit A Discharge Transducer
19
12002
Circuit B Discharge Transducer
20
12003
Circuit C Discharge Transducer
21
12004
Circuit A Suction Transducer
22
12005
Circuit B Suction Transducer
23
12006
Circuit C Suction Transducer
24
12010
Circuit A Oil Pressure Transducer
25
12011
Circuit B Oil Pressure Transducer
26
12012
Circuit C Oil Pressure Transducer
27
12013
Circuit A Economizer Pressure Transducer
28
12014
Circuit B Economizer Pressure Transducer
29
12015
Circuit C Economizer Pressure Transducer
Communication failures
30
4101
Loss of communication with Compressor
Board A
31
4201
Loss of communication with Compressor
Board B
32
4301
Loss of communication with Compressor
Board C
33
4901
Loss of communication with SIOB Board A
34
4902
Loss of communication with SIOB Board B
35
4903
Loss of communication with SIOB Board C
36
4906
Loss of communication with SIOB Board
EMM
37
4907
Loss of communication with SIOB Board
DGT
38
4501
Loss of communication with Aux Board
Number 1 (leak detection option board)
Process failures and other
39
10001
Cooler Freeze Protection
40
10002
Circuit A Condenser Freeze
41
10003
Circuit B Condenser Freeze
42
10004
Circuit C Condenser Freeze
43
10005
Circuit A Low Suction Temperature
44
10006
Circuit B Low Suction Temperature
45
10007
Circuit C Low Suction Temperature
Reset type
Automatic, if thermistor
reading returns to normal
As above
As above
As above
As above
Not applicable to this unit
Automatic, if sensor voltage
reading returns to normal
As above
Not applicable to this unit
Automatic, if sensor voltage
reading returns to normal
As above
Not applicable to this unit
Automatic, if sensor voltage
reading returns to normal
As above
Not applicable to this unit
Automatic, if sensor voltage
reading returns to normal
As above
Not applicable to this unit
Automatic, if communication
is re-established
As above
Not applicable to this unit
Automatic, if communication
is re-established
As above
Not applicable to this unit
Automatic, if communication
is re-established
As above
As above
Manual
Automatic (if saturated
discharge temperature is
above 4.4°C) or Manual
As above
Not applicable to this unit
Automatic (the first alarm
within 24 hours) or Manual
As above
Not applicable to this unit
Action taken
Circuit A shuts down
Circuit B shuts down
Alert
Economizer function
disabled
As above
Circuit A shuts down
Circuit B shuts down
Circuit A shuts down
Circuit B shuts down
Circuit A shuts down
Circuit B shuts down
Circuit A shuts down
Circuit B shuts down
Unit shuts down
Unit shuts down
Unit shuts down
Unit shuts down
Unit shuts down
Unit shuts down
Circuit A shuts down OR
circuit B shuts down
Unit shuts down
Circuit A shuts down, but
the pump is running
Circuit B shuts down, but
the pump is running
Circuit A shuts down
Circuit B shuts down
Possible cause
Defective thermistor
As above
As above
As above
As above
Defective transducer
As above
Defective transducer
As above
Defective transducer
As above
Defective transducer
As above
Bus installation fault,
communication error
As above
Bus installation fault,
communication error
As above
Bus installation fault,
communication error
As above
As above
No water flow, defective
thermistor
Discharge pressure
transducer defective,
refrigerant leak or low
condenser water
temperature
As above
Pressure sensor
defective, EXV blocked
or lack of refrigerant
As above
31