No.
Code
Alarm description
46
10008
Circuit A High Superheat
47
10009
Circuit B High Superheat
48
10010
Circuit C High Superheat
49
10011
Circuit A Low Superheat
50
10012
Circuit B Low Superheat
51
10013
Circuit C Low Superheat
52
10014
Customer Interlock Failure
53
10028
Electrical Box Thermostat
54
10029
Loss of communication with System
Manager
55
10030
Master/Slave communication Failure
56
10067
Circuit A Low Oil Pressure
57
10068
Circuit B Low Oil Pressure
58
10069
Circuit C Low Oil Pressure
59
10070
Circuit A Max Oil Filter Differential Pressure
60
10071
Circuit B Max Oil Filter Differential Pressure
61
10072
Circuit C Max Oil Filter Differential Pressure
62
10084
Circuit A High Oil Filter Drop Pressure
63
10085
Circuit B High Oil Filter Drop Pressure
64
10086
Circuit C High Oil Filter Drop Pressure
65
10075
Circuit A Low Oil level
66
10076
Circuit B Low Oil level
67
10077
Circuit C Low Oil level
68
90-nn
Master chiller configuration error
69
8000
No factory configuration
70
7001
Illegal factory configuration
71
10031
Unit is in CCN emergency stop
72
10032
Cooler pump #1 fault
73
10033
Cooler pump #2 fault
74
10015
Condenser Flow Switch Failure
75
10037
Circuit A High Condensing Out Of Map
compressor
76
10038
Circuit B High Condensing Out Of Map
compressor
77
10039
Circuit C High Condensing Out Of Map
compressor
78
10073
Condenser pump #1 fault
79
10074
Condenser pump #2 fault
32
Reset type
Manual
Manual
Not applicable to this unit
Manual
Manual
Not applicable to this unit
Automatic (the first alarm
within 24 hours) or Manual
Automatic, if the safety
input is closed
Automatic, if communication
is re-established
As above
Manual
Manual
Not applicable to this unit
Manual
Manual
Not applicable to this unit
Manual
Manual
Not applicable to this unit
Automatic (three alarms
within 24 hours) or Manual
As above
Not applicable to this unit
Automatic, if master/slave
configuration returns to
normal or the unit returns to
the standalone mode
Automatic, if configuration
is provided
Automatic, if configuration
is corrected
Automatic, if operating
conditions return to normal
Manual
Manual
Automatic (the first alarm
within 24 hours) or Manual
Automatic
Automatic
Not applicable to this unit
Manual
Not applicable to this unit
Action taken
Circuit A shuts down
Circuit B shuts down
Circuit A shuts down
Circuit B shuts down
Unit shuts down
Unit shuts down
Unit returns to the stand-
alone mode
Master/slave control disabled As above
Circuit A shuts down
Circuit B shuts down
The affected compressor is
stopped, the second
compressor continues to run
As above
Circuit A shuts down
Circuit B shuts down
Circuit A shuts down
Circuit B shuts down
Master/slave operation is
disabled and the unit returns
to the stand-alone mode
Unit cannot be started
Unit cannot be started
Unit shuts down
Unit is restarted with another
pump running. If no pump is
available, the unit shuts down
As above
Condenser pump is stopped Condenser flow switch
Circuit A shuts down
Circuit B shuts down
Unit shuts down
Possible cause
Pressure sensor
defective, EXV blocked
or lack of refrigerant
As above
Pressure sensor
defective, EXV blocked
or lack of refrigerant
As above
Customer interlock
closed
Electrical box fault:
Control box poorly
ventilated or poor
electrical connection
CCN bus installation
defective
Pressure sensor fault,
defective wiring or oil
filter installation fault
As above
Pressure sensor fault,
defective wiring or oil
filter installation fault
As above
Pressure sensor fault,
wiring defective, oil filter
installation fault
As above
Oil level too low or oil
level detector defective
As above
Configuration failure
No factory configuration
Incorrect unit
configuration
Network emergency stop
command
Pump overheats or poor
pump connection
As above
open
Defective transducer
As above
Pump overheats or poor
pump connection