Carrier Touch Pilot Manual page 15

For 61xwhze heat pumps
Table of Contents

Advertisement

General Parameters Menu – GENUNIT (continued)
No.
Name
11
SP_OCC
12
CAP_T
13
TOT_CURR
14
CURR_LIM
15
sp
16
CTRL_PNT
17
EMSTOP
18
DEM_LIM
*Depends on the selected language (English by default).
Temperatures Menu – TEMP
No.
Name
1
COOL_EWT
2
COOL_LWT
3
COND_EWT
4
COND_LWT
5
SCT_A
6
SST_A
7
SUCT_A
8
DGT_A
9
CP_TMP_A
10
SCT_B
11
SST_B
12
SUCT_B
13
DGT_B
14
CP_TMP_B
15
SCT_C
16
SST_C
17
SUCT_C
18
DGT_C
19
CP_TMP_C
20
SPACETMP
21
CHWSTEMP
22
CHWSHEAT
23
ECO_TP_A
24
ECO_TP_B
2
ECO_TP_C
26
SUBC_T_a
27
SUBC_T_b
28
SUBC_APa
29
SUBC_APb
*Depends on the selected language (English by default).
Status
Unit
no/yes
-
0 to100
%
-
A
0 to 4000
A
-
°C
-
°C
dsable/enable
-
0 to 100
%
Status
Unit
-
°C
-
°C
-
°C
-
°C
-
°C
-
°C
-
°C
-
°C
-
°C
-
°C
-
°C
-
°C
-
°C
-
°C
-
°C
-
°C
-
°C
-
°C
-
°C
-
°C
-
°C
-
°C
-
°C
-
°C
-
°C
-
°C
-
°C
-
°C
-
°C
Displayed text*
Setpoint Occupied?
Percent Total Capacity
Actual Chiller Current
Chiller Current Limit
Current Setpoint
Control Point
Emergency Stop
Active Demand Limit Val
Displayed text*
Cooler Entering Fluid
Cooler Leaving Fluid
Condenser Entering Fluid
Condenser Leaving Fluid
Saturated Cond Tmp cir A
Saturated Suction Temp A
Compressor Suction Tmp A
Discharge Gas Temp cir A
Motor Temperature cir A
Saturated Cond Tmp cir B
Saturated Suction Temp B
Compressor Suction Tmp B
Discharge Gas Temp cir B
Motor Temperature cir B
Saturated Cond Tmp cir C
Saturated Suction Temp C
Compressor Suction Tmp C
Discharge Gas Temp cir C
Motor Temperature cir C
Optional Space Temp
CHWS Temperature
CHWS Heat Temp
Economizer Gas Temp A
Economizer Gas Temp B
Economizer Gas Temp C
cond Liquid Temp A
cond Liquid Temp B
Apparent Subcooling A
Apparent Subcooling B
Description
Setpoint occupancy status:
no = unoccupied
yes = occupied
Total unit capacity
Actual chiller current
Chiller current limit
Current setpoint
Control point: Water temperature that the unit must
produce (active setpoint + reset)
Emergency stop: Used to stop the unit regardless of
its active operating type
Active demand limit value: When the unit is in Network
mode, the minimum value will be used compared to
the status of the external limit switch contact and the
demand limit switch setpoint
Description
Evaporator entering water temperature: Used for
capacity control
Evaporator leaving water temperature: Used for
capacity control
Condenser entering fluid temperature
Condenser leaving fluid temperature
Saturated condensing temperature, circuit A
Saturated suction temperature, circuit A
Compressor suction temperature, circuit A
Discharge gas temperature, circuit A
Motor temperature, circuit A
Saturated condensing temperature, circuit B
Saturated suction temperature, circuit B
Compressor suction temperature, circuit B
Discharge gas temperature, circuit B
Motor temperature, circuit B
Not applicable to this unit
Not applicable to this unit
Not applicable to this unit
Not applicable to this unit
Not applicable to this unit
Space temperature (EMM option)
Master/Slave common water temperature
Not available
Economizer gas temperature, circuit A
Economizer gas temperature, circuit B
Not applicable to this unit
Condenser liquid temperature, circuit A
Condenser liquid temperature, circuit B
Apparent Subcooling, circuit A
Apparent Subcooling, circuit B
15

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents