General Configuration Menu – GEN_CONF(continued)
No.
Name
Status
25
ice_cnfg
no/yes
26
al_rever
no/yes
*Depends on the selected language (English by default).
Pump Configuration Menu – PUMPCONF
No.
Name
Status
1
hpumpseq
0 to 4
2
cpumpseq
0 to 4
3
4
5
6
7
8
pump_del
24 to 3000
9
pump_per
no/yes
10
pump_sby
no/yes
11
pump_loc
no/yes
12
stopheat
no/yes
13
stopcool
no/yes
*Depends on the selected language (English by default).
User Configuration Menu – USERCONF
No.
Name
Status
1
use_pass
0 to 9999
*Depends on the selected language (English by default).
Reset Configuration Menu – RESETCFG
No.
Name
Status
1
cr_sel
0 to 3
2
hr_sel
0 to 3
3
4
5
6
7
8
dt_cr_no
0 to 13.9
9
dt_cr_fu
0 to 13.9
10
v_cr_no
0 to 20
11
v_cr_fu
0 to 20
12
spacr_no
-10 to 51.7
13
spacr_fu
-10 to 51.7
14
cr_deg
-16.7 to 16.7
20
Default
Unit
Displayed text*
no
-
Ice Mode Enable
no
-
Reverse Alarms Relay
Default
Unit
Displayed text*
0
-
Condenser Pumps Sequence
0
-
Cooler Pumps Sequence
0 = No Pump
1 = One Pump Only
2 = Two Pumps Auto
3 = Pump#1 Manual
4 = Pump#2 Manual
48
hour
Pump Auto Rotation Delay
no
-
Pump Sticking Protection
no
-
Stop Pump During Standby
yes
-
Flow Checked If Pump Off
no
-
Cooler Pump Off In Heat
no
-
Cond Pump Off In Cool
Default
Unit
Displayed text*
11
-
User Password
Default
Unit
Displayed text*
0
-
Cooling Reset Select
0
-
Heating Reset Select
0=None, 1= Delta T
2=4-20mA control T
3= Space Temp
Cooling
0
^C
Delta T No Reset Value
0
^C
Delta T Full Reset Value
0
mA
Current No Reset Value
0
mA
Current Full Reset Value
-10
°C
Space T No Reset Value
-10
°C
Space T Full Reset Value
0
^C
Cooling Reset Deg. Value
Description
Ice mode enabled
Alarm / Alert signals reverted
No = standard operation
Yes = alarm/alert/shutdown outputs are "On" even
if there is no alarm/alert (alarm output unavailable)
Description
Condenser pumps' sequence: This unit can
control only one condenser pump. This value
can be set to "0" or "1".
Evaporator pumps' sequence
0 = No Pump
1 = One Pump Only
2 = Two Pumps Auto (units with two pumps)
3 = Pump#1 Manual
4 = Pump#2 Manual
Pump auto rotation delay (units with two
pumps = auto control)
Pump anti-sticking protection
Not applicable to this unit
Water flow is checked when the pump is off
Evaporator pump OFF in heating
Condenser pump OFF in cooling
Description
User password: The user password can be
modified by changing the value in this line
Description
Cooling reset selection
Heating reset selection
0 = None, 1 = Delta T
2 = 4-20mA control
3 = Space temperature
Cooling
Delta T, no reset value
Delta T, max. reset value
Current, no reset value
Current, max. reset value
Space temperature, no reset value
Space temperature, max. reset value
Maximum cooling reset value