Troubleshooting
I/O Module Compatible
Event Number: 63
Event Classification: Severe / Fatal Event
Action: Verify that the type of I/O module installed matches what was selected
* Fail I/O Jumper Check
Event Number: 64
Event Classification: Severe / Fatal Event
Action: Verify that the type of I/O module installed matches what was selected
Pass I/O Jumper Check
Event Number: 65
Event Classification: Severe / Fatal Event
Action: Verify that the type of I/O module installed matches what was selected
Fail Main Board +5V-A
Event Number: 100
Event Classification: Potential Problem
Action: Verify that noise from the power source is not causing the problem. If
Pass Main Board +5V-A
Event Number: 101
Event Classification: Potential Problem
Action: Verify that noise from the power source is not causing the problem. If
Fail Main Board +5V-B
Event Number: 102
Event Classification: Potential Problem
Action: Verify that noise from the power source is not causing the problem. If
196
in the software. If the correct I/O module is installed, there may be a
fault with the Monitor Module or the Monitor I/O module.
in the software. If the correct I/O module is installed, there may be a
fault with the Monitor Module or the Monitor I/O module.
Monitor Module will stop alarming.
in the software. If the correct I/O module is installed, there may be a
fault with the Monitor Module or the Monitor I/O module.
(Fail Main Board +5V - upper Power Supply)
the problem is not caused by noise, check to see if one of the following
components is faulty:
- the Monitor Module
- the Power Supply installed in the upper slot
(Pass Main Board +5V - upper Power Supply)
the problem is not caused by noise, check to see if one of the following
components is faulty:
- the Monitor Module
- the Power Supply installed in the upper slot
(Fail Main Board +5V - lower Power Supply)
the problem is not caused by noise, check to see if one of the following
components is faulty:
- the Monitor Module
- the Power Supply installed in the lower slot
3500/42 Operation and Maintenance