Maintenance
Differential Expansion Ok Limits and Center Gap Voltage
Transducer
25 mm
35 mm
50 mm
Transducer
barrier
3300 5mm
-16.75
3300 8mm
-16.75
7200 5mm
-16.75
7200 8mm
-16.75
7200 11mm
-19.65
7200 14mm
-16.75
3300 16mm
-16.75
HTPS
Note: With Barriers includes BNC Internal Barrier I/O Modules.
188
Upper Ok Limits
-12.55
-12.55
-12.55
Eccentricity Ok Limits and Center Gap Voltage
Upper Ok Limits
w/o
w/ barrier
(V)
barrier
(V)
-16.75
-16.75
-16.75
-16.75
n/a
n/a
n/a
3500/42 Operation and Maintenance
Lower Ok Limits
-1.35
-1.35
-1.35
Lower Ok Limits
w/o
w/ barrier
(V)
barrier (V)
(V)
-2.75
-2.75
-2.75
-2.75
-2.75
-2.75
-2.75
-2.75
-3.55
n/a
-2.75
n/a
-2.75
n/a
Center Gap Voltage
-6.95
-6.95
-6.95
Center Gap Voltage
w/o
w/ barrier
(V)
-9.75
-9.75
-9.75
-9.75
-9.75
-9.75
-9.75
-9.75
-11.6
n/a
-9.75
n/a
-9.75
n/a