* Configuration Failure
Event Number: 301
Event Classification: Severe/Fatal Event
Action: Download a new configuration to the Monitor Module. If the problem
Configuration Failure
Event Number: 301
Event Classification: Potential Problem
Action: Download a new configuration to the Monitor Module. If the problem
* Module Entered Cfg Mode
Event Number: 302
Event Classification: Typical Logged Event
Action: No action required.
Software Switches Reset
Event Number: 305
Event Classification: Potential Problem
Action: Download the software switches to the Monitor Module. If the
Internal Cal Reset
Event Number: 307
Event Classification: Severe/Fatal Event
Event Specific:
Action: Replace Monitor Module immediately.
Monitor TMR PPL Failed
Event Number: 310
Event Classification: Potential Problem
Action: Replace the Monitor Module.
Monitor TMR PPL Passed (Monitor TMR Proportional value Passed)
Event Number: 311
Event Classification: Potential Problem
Action: Replace the Monitor Module.
Module Reboot
Event Number: 320
Event Classification: Typical Logged Event
Action: No action required.
200
still exists replace the Monitor Module immediately.
Monitor Module will stop alarming.
still exists replace the Monitor Module as soon as possible.
Monitor Module will stop alarming.
software switches are not correct, replace the Monitor Module as soon
as possible.
(Internal Calibration Reset)
Ch pair x
(Monitor TMR Proportional value Failed)
3500/42 Operation and Maintenance
(Module Entered Configuration Mode)

Advertisement