4. Select the monitor channel to be adjusted in the Monitor Channel list box.
5. For all measurement parameters except phase, adjust the setpoint level by
dragging the bar in the bar graph or by entering a value in the text box above
or below the parameter.
Notice that setpoints can be adjusted only for those parameters that are
enabled and that some parameters have both upper and lower setpoint
values. Parameters are enabled or disabled by using the Channel Option
screen. Refer to the 3500 Monitoring System Rack Configuration and
Utilities Guide for more information.
6. For phase setpoints, enter the values for the beginning and ending setpoint in
the text boxes below the phase diagrams.
7. Apply the adjusted setpoints to the rack by clicking OK and then downloading
the revised configuration to the rack.
3.2

Replacing modules

The boards and components inside of 3500 modules cannot be repaired in the
field and require no calibration. For 3500 modules that are not operating
properly, use the information in this section to replace the module with a spare
and then contact your local Bently Nevada representative for information about
returning the faulty module for failure analysis.
3.2.1
Replacing a main module
1. Save the configuration of the module to be replaced.
3500 modules must have valid configuration settings in order to operate
properly. Replacement modules are not configured. By saving the
configuration, you can download the original configuration settings to the
replacement module.
The 3500 Monitoring System Configuration and Utilities Guide, part number
129777-01, shows how to save configuration files.
22