2. Remove the module to be replaced.
Refer to Removing and inserting a main module on page 24.
3. Insert the new module
Refer to Removing and inserting a main module on page 24.
4. Download the configuration to the new module.
The 3500 Monitoring System Configuration and Utilities Guide, part number
129777-01, shows how to download configuration files.
5. Verify operation.
-
Check that the LEDs for the replaced module are indicating correct
operation (see Reading the LEDs on page 16).
The values of the measurement parameters of a channel are verified by
-
using the Verification utility in the 3500 Rack Configuration program and
the verification procedure in the reference manual for that module.
3.2.2

Replacing an I/O module

This procedure applies only to the I/O module of a monitor or the PIM of a power
supply that is to be replaced. Prior to removing any module, refer to the
applicable reference manual to see how rack behavior may be affected and for
any special handling requirements required for personal safety.
1. If necessary, upload and save the configuration of the module to be replaced.
3500 modules must have valid configuration settings in order to operate
properly. Replacement modules are not configured. By saving the
configuration, you can download the original configuration settings to the
replacement module.
The 3500 Monitoring System Configuration and Utilities Guide, part number
129777-01, shows how to save configuration files.
2. Remove the main module from the rack.
Refer to Removing and inserting a main module on page 24.
3. Remove the field wiring from the I/O module.
If the wires connected to the I/O module are not labeled, label the wires
before you remove them.
4. Remove the old I/O module from the rack.
5. Install the new I/O module into the rack.
6. Connect the field wiring to the new I/O module.
7. Install the main module into the rack.
Refer to Removing and inserting a main module on page 24.
8. Download the configuration to the new module.
The 3500 Monitoring System Configuration and Utilities Guide, part number
129777-01, shows how to download configuration files.
9. Verify operation.
Section 3 — Common maintenance procedures