Output Electrical Specifications - Huawei UPS2000-G-3KRTLL User Manual

Hide thumbs Also See for UPS2000-G-3KRTLL:
Table of Contents

Advertisement

UPS2000-G-3KRTLL
User Manual
Item
Bypass voltage
range
Bypass frequency
Input frequency
range
Bypass overload
capability
Transient
withstand current
Input mode

7.5 Output Electrical Specifications

Table 7-5 Output electrical specifications
Item
Rated capacity
Output power factor
Rated output voltage
Output voltage precision
Output frequency
System efficiency
Waveform (battery mode)
THDv
Issue 01 (2020-10-26)
Specifications
176–280 V AC
50 Hz/60 Hz
● 50 Hz/60 Hz±4 Hz
Load ≤ 125%: continuous working
125% < load ≤ 150%: disconnect the output after 1 minute
150% < load: disconnect the output after 100 ms
Load in bypass mode = Output current/Rated output
current
10 kA
The mains input and bypass input share a power source.
Copyright © Huawei Technologies Co., Ltd.
Specifications
3 kVA/2.7 kW
0.9
220 V AC/230 V AC/240 V AC
±1%
● When the mains is normal, the UPS
automatically tracks the mains frequency.
● When the mains is abnormal, the output
frequency is 50 Hz (tolerance ±0.5%).
● Maximum efficiency: ≥ 93%
● 100% load: ≥ 93%; 50% load: ≥ 92%; 30%
load: ≥ 90%
Sine wave
● < 7% (non-resistive loads)
● < 3% (resistive loads)
7 Technical Specifications