UPS2000-G-3KRTLL
User Manual
Name
Float charge
voltage
Battery (EOD)
point
Set the
communications
address
Issue 01 (2020-10-26)
Display
Copyright © Huawei Technologies Co., Ltd.
4 Control Panel
Description
● Default value: 54.0 V
● When the lithium
battery does not
communicate, the
value range is 51.0–
56.0 V. The value
increases by 0.1 V
each time you press
SELECT.
● When the lithium
battery is
communicating, the
UPS automatically
adapts to the float
charging voltage
based on the
connected lithium
battery model. The
value is fixed and
cannot be changed.
● Default value: 44.0 V
● Value range: 44.0–
46.0 V. The value
increases by 0.1 V
each time you press
SELECT. The battery
EOD threshold is
fixed at the current
value regardless of
the load percentage.
The default
communications
address is 001, which is
used for the RS485
communications ports
(connect to northbound
devices). Set different
communications
addresses for parallel
UPSs.
50