Huawei UPS2000-G-3KRTLL User Manual page 53

Hide thumbs Also See for UPS2000-G-3KRTLL:
Table of Contents

Advertisement

UPS2000-G-3KRTLL
User Manual
Name
Battery discharge
time
Battery capacity
Output frequency
Issue 01 (2020-10-26)
Display
Copyright © Huawei Technologies Co., Ltd.
4 Control Panel
Description
● Default value: 0H
(this function is
disabled)
● Value range: 0H–
48H
● Default value: 100
Ah; value range: 50–
2400 Ah. The value
increases by 50 Ah
each time you press
SELECT.
● Battery string
sharing enabled:
When setting the
battery capacity, set
the total battery
string capacity for
each UPS.
● Battery string
sharing disabled:
When setting the
battery capacity, set
the capacity of the
battery string
connected to each
UPS.
You need to shut down
the inverter before
changing the output
frequency.
● 50 Hz (default)
● 60 Hz
47