3.8 ISO I/O Cable Installation

8400-M117-O1 Rev D
3.8.1. The ISO I/O wires are to be connected to the P2 terminal block on
the bottom panel of the weight transmitter. Refer to Figure No. 2B
for an illustration of the connector layout.
3.8.2. Remove the 10-connector terminal block connector from the weight
transmitter. Grasp the terminal block connector and lift straight up
away from the enclosure.
3.8.3. Referring to the table below and the labels on the enclosure for
terminal connections, connect each wire to the terminal block.
3.8.4. Remove 2" of the outer insulation jacket then remove 1/4" of
insulation from each of the wires.
3.8.5. To terminate a wire, push down on the orange spring loaded
plunger and then insert the wire into the terminal opening. Release
the plunger to secure the wire in place.
3.8.6. Repeat the procedure until all wires are in place.
Terminal
1
2
3
4
5
P2 Terminal Block
Connector
CPN - 6610-1548
Model 201 Installation & Technical
P2 – ISO I/O Wiring Table
Function
Terminal
12-24 VDC
IN1
IN2
IN3
IN4
Orange
Plunger
Function
6
COM
7
OUT1
8
OUT2
9
OUT3
10
OUT4
P2 Socket
Page 17