UL 8th Edition Panel Applications
Annunciator Point Types
The annunciator types for this panel will display according to the NCA-2 Column in Table F.5.
CAUTION:
!
When using the NCA-2 to annunciate points on the AM2020/AFP-1010 over the network, enable state reporting in the
AM2020/AFP-1010 panel for control module points and "NONA"NOA" module points. Otherwise, any changes in the state of
these points on the FACP will not be annunciated over the network to annunciator points mapped to the NCA-2.
1. Choose option "I=PSYS" from the FACP programming menu for partial system programming.
2. Choose option "6=EXTEQ".
3. Answer YES to the following questions:
• DO YOU WANT TO CHANGE THE CONTROL MODULE STATE REPORTING?
• DO YOU WANT TO REPORT CONTROL MODULE STATE CHANGES?
• DO YOU WANT TO CHANGE THE "NONA"/"NOA" MDULE STATE REPORTING?
• DO YOU WANT TO REPORT "NONA"/"NOA" MODULE STATE CHANGES?
OR, if completely programming the panel:
1. Choose option "2-FSYS".
2. Answer YES to the following questions:
• DO YOU WANT TO REPORT CONTROL MODULE STATE CHANGES?
• DO YOU WANT TO REPORT "NONA"/"NOA" MODULE STATE CHANGES?
.
AFP-1010/AM2020
Annunciator Point Type
F.3 AFP-300/AFP-400
Device Point Types
The device types for this panel will display on the NCA-2 as follows:
96
AFP-1010/AM2020
Device Point Type
TRBLES PEND
TRBL MONITOR
CMX CONTROL
CMX FORM C
NON ALM MON
GN ALARM EVC
GN ALARM
GN ALARM FORC
GN WATER FLW
GN TRBL FORC
GN WAT FORC
GN SUPR FORC
Table F.4 NCA-2 Display for AM2020/AFP-1010 Device Point Types
NCA-2 Displays:
AMAN
MANUAL
AAST
ACKNOWLEDGE
ASGS
SILENCE
ARES
RESET
ALMP
NONE
AZON
MONITOR
ADET
MONITOR
Table F.5 NCA-2 Display for AM2020/AFP-1010 Annunciator Point Types
AFP-300/AFP-400
Device Point Type
HEAT(ANALOG)
MULTISENSOR
SUPERVISORY
Table F.6 NCA-2 Display for AFP-300/AFP-400 Device Point Types
NCA-2 Displays:
TROUBLE PEND
TROUBLE MON
CONTROL
FORM C RESET
NON FIRE
GEN ALARM
GEN ALARM
GEN ALARM
GEN ALARM
GEN TROUBLE
GEN ALARM
GEN SUPERVIS
AFP-1010/AM2020
Annunciator Point Type
AMON
AINP
ACON
ATEL
ASUP
AFCM
NCA-2 Displays:
HEAT
SMOKE(MULTI)
TRACK SUPERV
AFP-300/AFP-400
AFP-1010/AM2020
NCA-2 Displays:
Device Point Type
ION DUCT DET
SMOKE(DUCT I)
NON ALARM
FORMC MANUAL
SYSTEM MONTR
SYS MONITOR
DACT CONNECT
GEN TROUBLE
SPRVSRY MNTR
TRACK SUPERV
SMOKE ION HP
SMOKE(DUCT I)
SMOKE ION LP
SMOKE(DUCT I)
SMOKE(COMBO)
SMOKE(MULTI)
SMOKE(PHOTV)
SMOKE(PHOTO)
SMOKE(IONV)
SMOKE(ION)
NCA-2 Displays:
MONITOR
MONITOR
CONTROL
TELEPHONE
MONITOR
CONTROL
NCA-2 Manual — P/N 52482:M5 03/20/2019
NON FIRE
RELAY