E.3: Australia; E.4: China; E.5: Canada - Honeywell NOTIFIER NCA-2 Instruction Manual

Network control annunciator
Hide thumbs Also See for NOTIFIER NCA-2:
Table of Contents

Advertisement

Australia
E.3 Australia
The REGIONAL SETTING choice of AUSTRALIA activates the following features:
• allows use of the Australian smoke control module SCS-8AU.
• "Brigade Act" LED is controlled by ZL1000.
• Test LED is lit during walktest.
• Special passwords for testing memory corruption detection.
"Corrupta" will temporarily corrupt a location in the application.
"Corruptb" will temporarily corrupt a location in the boot.
"Corruptd" will temporarily corrupt a location in the database.
"Remove corruption" will uncorrupt the panel and reboot.
• Plant Isolate button will disable/enable ZL999.
• No softkeys on the panel will function while there is an unacknowledged alarm EXCEPT scroll, silence, reset and disable.
• Silence key acknowledges everything before silencing.
• Disable key disables the current event on the screen.
• Fan control function per AS/NZS 1668:1:1998, section 4.13.2.
• First zone in alarm displayed at top of display. Additional zones in alarm also displayed, until panel reset. Alarm zones not
currently on display may be viewed using the scroll button.
• Security events will light the supervisory LED. The supervisory scroll key will scroll through security events.
• Pre-alarm events will be displayed after alarms.
• The Main Menu includes an "Other events" menu key to scroll through other events.
• Password Bypass Timer enabled. After entering a valid password, the user does not need to enter a password again until no key
is pressed for ten minutes.
• Active Output events are displayed if Output Activations are enabled in the Event Logging menu.
• Disable/Enable button will disable or enable the currently-displayed event.
• AMPS-24 supervision disabled.
• When the primary supply is not an AMPS-24, selecting AUX trouble supervisory setting will generate a general power supply
fault.
E.4 China
REGIONAL SETTING
The
• POM-8a support
• Active output events displayed. A counter is displayed for active outputs.
• Municipal Communication panel settings
• New special function zone for alarm verification
• Prealarm automatically cleared after five minutes
• Co-op detectors alarm functions
• Dual alarm window
• Points in trouble will not activate
• Ten minute limit for DEL and SDEL delay functions
• Disable events do not light LED or trip the trouble relay
• No system trouble generated upon entering program mode
• Low AC operation of FACP
• Power supply troubles.
E.5 Canada
The REGIONAL SETTING choice of CANADA:
• Two-Stage coded systems (3/5 minute timer) - An ACM-24AT control point mapped to Special Function zone ZF39 is required
for Automatic Alarm Signal Cancel. Acknowledge will not cancel the Two-Stage timer
• Multiple Display and Control Centers (DCC) - An ACM-24AT programmed as 96DCC is required to provide ACS monitor
points to indicate which DCC is in control.
If the Display and Control Center (DCC) feature is enabled:
-An ACS control point mapped to the local Special Function zone ZF36 is required
-An ACS monitor point mapped to ZF36 for each DCC and node that has DCC enabled on the network is required
• If an LCD-160 is connected to the NCA-2 and DCC is enabled, Local Control should be disabled
• A Signal Silence or System Reset is required to clear an Alarm Signal
• Annunciator Applications:
-ACS points programmed as Acknowledge, Signal Silence, System Reset, and Drill do not function
-ACM points programmed for Alarm Signal Cancel should be labeled as "Automatic Alarm Signal Cancel" or "Auto Alm Signal
Cancel"
-The following LED colors must be employed:
• Red must be used to indicate fire alarms
Yellow must be used to indicate supervisory, burglary, trouble signals, and Automatic Alarm Signal Cancel
Green must be used to indicate the presence of power or an activated output
NCA-2 Manual — P/N 52482:M5 03/20/2019
CHINA
choice of
activates the following features:
Regional Settings
93

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents