while holding it down, turn the panel on and re-
lease the push-button when the unit has started
up
Alarm: the red 'service' light is lit.
Cause: 100 hours have elapsed since the latest
engine oil change and engine oil should be
changed.
How to reset the alarm: turn on the panel and
wait for the generating set to start. Now press the
button hidden under the small hole in the bottom
left corner (Fig.30 Ref.10) and release it immedi-
ately thereafter. Wait a couple of minutes before
turning the generating set off.
Alarm: the display unit shows random charac-
ters.
Cause: malfunctioning due to low voltage during
start-up (low battery, cable cross-section too
small). In this case, just turn Off and On the con-
trol panel.
In certain situations, data of internal microproc-
essor of the panel may be subject to permanent
alterations and prevent running of generating set.
In this case, to restore the functionality of panel is
necessary to completely re-initialize (contact the
Service).

6.7 Automatic Version (optional)

If you wish the start-up batteries to be recharged
automatically in the En 4010 G generating sets, it
is possible to install the ASP (optional) automatic
control panel (fig.32) instead of the manual con-
trol panel.
The elements making it up are:
1 ON/OFF switch for the start-up and switch-off
function
2 Display
3 High temperature indicator
18
GB
4 Minimum oil level indicator
5 Start-up failed indicator
6 Generator running indicator (flashing)
7 Maintenance request indicator
8 Fuel reserve indicator
9 Hour or voltmetric changeover switch button
10 Reset
11 Battery charged indicator
12 Automatic function indicator
13 AUTO/MAN switch for the automatic or man-
ual function

6.8 MANUAL operation

See section 6.1

6.9 AUTOMATIC operation

Turn the AUTO/MAN switch (Fig.32 Ref.13) to
the AUTO position and set the start-up switch
(Fig. 25 Ref. 1) to ON position.
The automatic function indicator (Fig.32 Ref.12)
will light up.
When the voltage at the ends of the 12V DC ter-
minals of the generating set is lower than 11.5
Volts, the generating set will begin the start-up
procedure (similar to that of the manual opera-
tion).
During the operation in automatic mode, the dis-
play (Fig.32 Ref.2) will show the total running
hours of the generating set. Press the hour or
voltmetric changeover switch button (Fig.32
Ref.9) to display the voltage at the ends of the
12V DC terminals, i.e. at the ends of the battery.
When the battery is charged, and anyway after at
least 15 minutes' running, the battery charged
hours indicator (Fig.32 Ref.11) will light up and
the electronic control panel will turn off the gen-
erating set.
manual mode is necessary to position the
AUTO / MAN switch before turning on the
panel with the ON / OFF switch.
Remember that the time which is taken by the
generating set in automatic mode to recharge the
battery may vary according to the battery status,
the amount of connected batteries and the ambi-
ent temperature.
Generally, the lower the temperature the less the
time required to charge the battery.