The generator can now be located on the previ-
ously drilled surface (fig.7) using the suitable vi-
bration-damping cylinders (fig. 10 ref. 1) and
spacers (fig. 10 rif.2)

4.3 Wiring connection instructions

By using the special key to open the lock, re-
move the front door.
Then remove the bottom surface locking screws
(Fig. 11 Ref. 2) on both sides.
Take out the bottom surface with the engine all
the way to the mechanical stop (Fig. 12).
If you wish to completely remove the engine sur-
face, screw out the locking screws (Fig. 11 Ref.
3), too.
10
GB

4.4 Battery connection

To start up the generating set, connection to the
battery of the vehicle must be provided using a
sheathed power cable up to current standards,
with the cross-section shown in Table 1.
To this end, the generating set is provided with
two special terminals (Fig.13 Ref.2) used to con-
nect the positive and negative poles of the bat-
tery.
Connect the cable of the positive pole (red cable)
to the terminal already having a red cable and
the cable of the negative pole (black pole) to the
terminal already having a black cable. The cable
of the negative pole must be of the same cross-
section as the positive cable, and must be con-
nected both to the negative pole of the battery
and to the vehicle chassis.
Make sure there is good contact; remove any
paint or rust from the contact surface, and protect
the connection by applying grease.
The capacity of the battery to be used for starting
up must not be less than 100 A/h.
The soundproofing box is equipped with two ca-
ble outlets used to let through the battery con-
nection cables (Fig. 11 Ref. 1).
The cable presser block is used to prevent water
seeping into the power generating set.
Energy 4010 G