Manual Operation; Automatic Operation; Control And Alarm Functions - Telair ENERGY 8012 GAS Use And Maintenance Manual And Instructions For Installation

Table of Contents

Advertisement

The elements making them up are:
1
ON/OFF switch for the start-up and switch-off
function
2
AUTO/MAN switch for the automatic or man-
ual function
3
Display
4
Hour or voltmetric switch button
5
Reset
6
Generator running indicator (flashing)
7
Automatic function indicator
8
Startup failed indicator
9
Maintenance request indicator
10 Fuel reserve indicator
11 Battery charged indicator
12 Minimum oil level indicator
13 High temperature indicator

6.2 MANUAL operation

Position the AUTO/MAN (2) switch on the MAN
position and set the startup switch (1) to ON posi-
tion. The word WAIT will appear on the display
(3) for 8 seconds. When these have run out, the
electronic control panel will start the first auto-
matic procedure for starting up the generating
set. If the engine starts up at the end of this
phase, then the generator running indicator (6)
will start to flash.
Should the engine not start up, this automatic
procedure will be repeated up to 4 times. If the
engine has not started up yet at the end of this
complete cycle, the startup failed indicator (8) will
light up. If only the startup failed indicator (8)
stays lit, you can repeat the startup procedure
several times.
If the generating set has not started up at all
even after many attempts, you will have to get in
touch with the after-sales service.
During the operation in manual mode, the display
(3) will show the total running hours of the gener-
ating set.
Press the hour or voltmetric switch button to dis-
play the running hours after the last mainte-
nance.

6.3 AUTOMATIC operation

Position the AUTO/MAN (2) switch on the AUTO
position and set the startup switch (1) to ON posi-
tion.
The automatic function indicator (7) will light up.
If the battery which supplies the generating set
has a voltage of more than 11.5 Volts, the battery
charged indicator (11) will light up.
When the voltage at the ends of the 12Vdc ter-
minals of the generating set is lower than 11.5
Vers. 001
GB
Volts, the battery charged light indicator (11) will
go off and the generating set will begin the
startup procedure (similar to that of the manual
operation).
During the operation in automatic mode, the dis-
play (3) will show the total running hours of the
generating set. Press the hour or voltmetric
switch button to display the voltage at the ends of
the 12Vdc terminals, or at the ends of the battery.
When the battery is charged, the battery charged
indicator (11) will light up and the electronic con-
trol panel will turn off the generating set.

6.4 Control and Alarm Functions

3 DISPLAY: when the generating set has started
up, the total running hours will be displayed.
Press the hour or voltmetric switch button during
the manual operation to display the running
hours after the last maintenance. Press the hour
or voltmetric switch button during the automatic
operation to display the voltage at the ends of the
12Vdc terminals, or at the ends of the battery.
4 HOUR and VOLTMETRIC SWITCH BUTTON:
when in MAN (2) function, press this button to
display the running hours elapsed after the last
change of the engine oil. When in AUTO (2) func-
tion, press this button to display the voltage at
the ends of the 12Vdc terminals.
5 RESET: when the display shows any charac-
ters without logic, the panel is to be reinitialised.
Press the Reset key and, holding it down, switch
on the panel. When 4 zeroes (0000) are shown
on the display, the panel is reinitialised.
6 GENERATOR RUNNING INDICATOR: this in-
dicator flashes during proper operation of the
generating set.
7 AUTOMATIC FUNCTION INDICATOR: this pi-
lot lamp is illuminated as long as the AUTO (2)
function is selected.
8 STARTUP FAILED INDICATOR: this pilot lamp
will light up to indicate that the generating set has
not started up, after all four attempts at starting
up have failed.
9 MAINTENANCE REQUEST INDICATOR: this
pilot lamp flashes after 50 running hours have
elapsed and the engine oil level is to be checked.
When the lamp illuminates steady, this means
that 100 running hours have elapsed and the en-
gine oil is to be changed. Upon every engine oil
Energy 8012 G
15