28
Device Description
The I/O module 750-601/040-000 meets the following EMC standards as these
standards relate to the I/O module:
Table 17: EMC – Immunity to Interference
Standard
Electrostatic Discharge
• EN 61000-4-2
• EN 60255-26
• IEEE C37.90.3
High-frequency Electromagnetic Fields
• EN 61000-4-3
• EN 60255-26
• IEEE C37.90.2
Fast Electrical Transient Disturbances / Burst
• EN 61000-4-4
• EN 60255-26
• IEEE C37.90.1
Surge Voltage / Surge
• EN 61000-4-5
• EN 60255-26
Conducted Disturbances, Induced by High-frequency Fields
• EN 61000-4-6
• EN 60255-26
Magnetic Fields With Electrical Frequencies
• EN 61000-4-8
• EN 60255-26
Pulse-shaped Magnetic Fields
• EN 61000-4-9
Damped Oscillatory Magnetic Fields
• EN 61000-4-10
Voltage Dips, Short-term Interruptions and Voltage Fluctuations
• EN 61000-4-11
• EN 60255-26
Damped Sinusoidal Oscillations
• EN 61000-4-12
Harmonics and Interharmonics
• EN 61000-4-13
Conducted Asymmetric Disturbances
• EN 61000-4-16
Manual
Version 2.0.0
WAGO I/O SYSTEM 750 XTR
750-601/040-000 Power Supply 24 VDC Fuse XTR
Test Value
8 kV (contact discharge)
8 kV (air discharge)
20 V/m (80 MHz ... 1 GHz)
10 V/m (1 GHz ... 3 GHz)
4 kV
1 kV (conductor/conductor)
2 kV (conductor/ground)
10 V (150 kHz ... 80 MHz)
300 A/m continuous / 1000 A/m for 1 s
300 A/m
100 A/m
Standard not applicable
1 kV (conductor/conductor)
2 kV (conductor/ground)
Standard not applicable
30 V continuous
300 V for 1 s