WAGO I/O SYSTEM 750 XTR
750-601/040-000 Power Supply 24 VDC Fuse XTR
3.6
Technical Data
3.6.1
Device Data
Table 8: Technical Data – Device
Width
Height (from upper edge of DIN-rail)
Depth
Weight
Degree of protection
3.6.2
Supply
Table 9: Technical Data – Supply
Current consumption,
system voltage
Power Supply via CAGE CLAMP
connectors
for ambient operating temperature
for ambient operating temperature
Voltage via power jumper contacts
Current
max.
Rated surge voltage
Fuse
1)
including residual ripple of 15%
3.6.3
Connection Type
Table 10: Technical Data – Field Wiring
Wire connection
Cross section
Stripped lengths
Table 11: Technical Data – Power Jumper Contacts
Power jumper contacts
max.
®
under laboratory conditions
−40 °C ... +55 °C
+55 °C ... +70 °C
via power jumper contacts
Device Description
12 mm
62.6 mm
100 mm
46.3 g
IP20
5 mA
24 VDC (power supply via SELV/PELV
power supply unit)
18 V ... 31,2 V (17,4 V ... 31,2 V)
18 V ... 28,8 V (17,4 V ... 28,8 V)
18 V ... 26,4 V (17,4 V ... 26,4 V)
24 VDC
6.3 A
1 kV
5 x 20 mm; T 6.3 A (not included)
Notice: Use UL-recognized fuses only!
®
CAGE CLAMP
0.25 mm² ... 2.5 mm² / AWG 24 ... 14
8 mm ... 9 mm / 0.33 in
Spring contact, self-cleaning, hard gold
plated
23
1)
1)
1)
Manual
Version 2.0.0