4.2 Normal mode to maintenance bypass mode
1.
Remove plastic-panel:
Loosen the plastic panel screws of the MBP and remove the plastic panel
as below.
2.
Rotate the 'Maintenance Bypass Switch':
Remove protective cover of 'Maintenance Bypass Switch' first, then rotate
the handle of 'Maintenance Bypass Switch' to the position of
'MAINTENANCE'.
3.
Turn down the 'Input switch':
Set the UPS to standby mode on the UPS , Then, turned down all the 'Input
switch' on the front panel of the MBP to 'OFF', operation sequence is
recommended with: UPS input switch UPS bypass switch UPS
Neutral switch.
87