Communications gateway module installation kit, for use with hfr systems to provide fieldbus communications abilities, for professional use only
Hide thumbs Also See for 24J415:
Table of Contents

Advertisement

Available Internal Data
Data
Byte
Bit
Type
60,
Integer
61
62,
Integer
63
64,
Integer
65
66,
Integer
67
68,
Integer
69
70,
Integer
71
72,
Integer
73
74,
Integer
75
76,
Integer
77
0
1
2
3
78
Bit
4
5
6
7
20
State or
Range
CGM Outputs to PLC Inputs for Monitoring Description
Red Chiller Temperature Actual: Integer value of the actual Red chiller temperature.
Depending on the system set up this is read in °C or °F
The value from the CGM is an integer and must be multiplied by 0.1 for the actual tempera-
ture.
Example: Word 60 = 238 = 23.8°C (unit chosen is °C)
Blue Inline Temperature Set Point: Integer value of the Blue inline temperature set point.
Depending on the system set up this is read in °C or °F
The value from the CGM is an integer and must be multiplied by 0.1 for the actual tempera-
ture.
Example: Word 62 = 1000 = 100.0°F (unit chosen is °F)
Blue Hose Temperature Set Point: Integer value of the Blue hose temperature set point.
Depending on the system set up this is read in °C or °F
The value from the CGM is an integer and must be multiplied by 0.1 for the actual tempera-
ture.
Example: Word 64 = 950 = 95.0°F (unit chosen is °F)
Red Inline Temperature Set Point: Integer value of the Red inline temperature set point.
Depending on the system set up this is read in °C or °
The value from the CGM is an integer and must be multiplied by 0.1 for the actual tempera-
ture.
Example: Word 66 = 900 = 90.0°F (unit chosen is °F)
Red Hose Temperature Set Point: Integer value of the Red hose temperature set point.
Depending on the system set up this is read in °C or °F
The value from the CGM is an integer and must be multiplied by 0.1 for the actual tempera-
ture.
Example: Word 68 = 1100 = 110.0°F (unit chosen is °F)
Blue Tank Temperature Set Point: Integer value of the Blue tank temperature set point.
Depending on the system set up this is read in °C or °F
The value from the CGM is an integer and must be multiplied by 0.1 for the actual tempera-
ture.
Example: Word 70 = 1050 = 105.0°F (unit chosen is °F)
Red Tank Temperature Set Point: Integer value of the Red tank temperature set point.
Depending on the system set up this is read in °C or °F
The value from the CGM is an integer and must be multiplied by 0.1 for the actual tempera-
ture.
Example: Word 72 = 300 = 30.0°C (unit chosen is °C)
Blue Chiller Temperature Set Point: Integer value of the Blue chiller temperature set point.
Depending on the system set up this is read in °C or °F
The value from the CGM is an integer and must be multiplied by 0.1 for the actual tempera-
ture.
Example: Word 74 = 320 = 32.0°C (unit chosen is °C)
Red Chiller Temperature Set Point: Integer value of the Red chiller temperature set point.
Depending on the system set up this is read in °C or °F
The value from the CGM is an integer and must be multiplied by 0.1 for the actual tempera-
ture.
Example: Word 76 = 350 = 35.0°C (unit chosen is °C)
Tank Material Level Status: The state of the level switches on the tank.
76543210 (bits)
00000001 = Red Tank Level Low On
00000010 = Red Tank Level Middle On
00000100 = Red Tank Level High On
00010000 = Blue Tank Level Low On
00100000 = Blue Tank Level Middle On
01000000 = Blue Tank Level High On