Starting An Opc Ua Server Module And An Configuration Personal Computer - Mitsubishi Electric MELSEC iQ-R Series User Manual

Server module, startup, mx opc ua module configurator-r
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

4.1
Starting an OPC UA Server Module and an
Configuration Personal Computer
OPC UA server module*1
Mount it on a base unit.*2
Switch the dot matrix LED display mode
switch to the right (SHOW).
Connect the OPC UA server module and the configuration personal computer on a 1:1 basis.*4
Turn the power of the system ON.
The ERR LED is flashing since an SD memory card is not inserted.
Insert an SD memory card.*5
*1 Perform the self-diagnostic test as necessary. (MELSEC iQ-R OPC UA Server Module User's Manual (Application))
*2 Do not use an electric screwdriver to attach and remove module fixing screws.
*3 Page 55 INSTALLATION AND UNINSTALLATION
*4 Page 47 System configuration for the initial setup, maintenance, and inspection
*5 Page 41 SD Memory Card
*6 Specify the following (the default security setting) for connection on the "Connection Setting" screen of the configuration tool.
Use the user authentication :Select the checkbox.
User name: RD81OPC96
Password: MITSUBISHI
*7 Perform these steps to change the setting of an OPC UA server module.
*8 Page 34 Network setting for connection
*7
Connect the OPC UA server module and the configuration personal computer
according to the network setting.*8
Start an operation.

4.1 Starting an OPC UA Server Module and an Configuration Personal Computer

Configuration personal computer
Install the configuration tool.*3
Start the configuration tool.
Select "Direct Connection" on the
"Target Setting" screen.*6
Format the SD memory card.
Update the setting of the OPC UA server module.
Set the setting for the OPC UA server module.
Write the setting to the OPC UA server module.
Update the setting of the OPC UA server module.
4 PROCEDURE BEFORE OPERATION