Overload Protection

The overload protection circuit will automatically reduce the output
voltage for short circuits and overcurrents to protect the Power Supply
from short-circuit currents and overcurrents.
When the output current falls within the rated range, the overload
protection function is automatically cleared.
Reference Graphs
Model with
Power Boost Function
Intermittent
operation
0
Maximum boost current
Note: Refer to Overload Protection on page 17

Overvoltage Protection

Consider the possibility of an overvoltage and design the system so
that the load will not be subjected to an excessive voltage even if the
feedback circuit in the Power Supply fails.
When an excessive voltage that is approximately 130% of the rated
voltage or higher is output, the output voltage is shut OFF, preventing
damage to the load due to overvoltage.
To reset the protection, turn OFF the input power for three minutes or
longer and then turn it back ON.
Reference Graph
Rated
output voltage
Variable range
0V
Note: Do not turn ON the power again until the cause of the
overvoltage has been removed.
10
Model without
Power Boost Function
Intermittent
operation
0
Rated current
Overvoltage
protection
Operating
Inrush Current, Startup Time, and Output Hold
Time
Input ON
AC input
voltage
Inrush current on input application
AC input
current
Output voltage
Startup time
Note: A maximum startup time of 1,000 ms is required. Construct a
system configuration that considers the startup time of other
devices.
Input OFF
96.5%
90%
Hold time