Data Format And Range Of Values Of The Actual Values; Data Format - Festo CPX-4AE-4AA-H Description/Commissioning

Hide thumbs Also See for CPX-4AE-4AA-H:
Table of Contents

Advertisement

Commissioning
Module parameter: forcing of channel 0 ... 3
Function number
Access to this module parameter is made via protocol-specific functions
è
Description
With the forcing function, the digital input and output values can be influenced
independently of the actually pending input and output signal.
Forcing can be defined for the entire terminal CPX via the "Force Mode" system
parameter
Parameterisation of "Force-Mode channel x"
Depending on the fieldbus protocol, "Force-Mode" is parameterised as follows:
Parameterisation of "Force State channel x"
The desired output word must be mapped in the "Force State" parameter bits of
the respective channel.
Values
Tab. 33 Description of the "Forcing of channel 0 ... 3" module parameter
9.5

Data format and range of values of the actual values

9.5.1

Data format

The data format determines how the actual values (analogue values) are transferred by terminal CPX
to the control system.
Data format
Input data
D15 D14
field
MSB
Value
VZ
Digital input value
1)
1) VZ = sign (0 = positive, 1 = negative)
Tab. 34 Data format of the module CPX-4AE-4AA-H
Value range -32768 ... 0 ... 32767
Festo — CPX-4AE-4AA-H — 2019-04a
 Description of the bus node.
 Description of system CPX.
è
By setting a parameter bit (e.g. for CPX-FB11)
By setting all parameter bits of the pertinent word to "blocked" or "Force
State" (e.g. for CPX-FB13)
Force-Mode channel 0 
0 = blocked (default)
1 = Force State
Force State channel 0 
0 = reset value (default)
1 = set value
D13 D12 D11 D10 D9 D8 D7 D6 D5 D4 D3 D2 D1 D0
 3:
...
 3:
...
LSB
45