Ul/C-Ul (Csa) Application Notes - Pro-face GP-2300 Series User Manual

Pro-designer compatible
Table of Contents

Advertisement

UL/c-UL (CSA) Application Notes

The GP2300-LG41-24V/GP2300-TC41-24V/GP2301-LG41-24V/GP2301-SC41-
24V/GP2301-TC41-24V units are UL/c-UL(CSA) listed products.
UL file no. E182139(UL60950+UL1604)
When applying for UL approval for a product that includes one of these GP units,
please be sure to pay special attention to the fact that all products with built-in GP
units require UL inspection of the combination of the GP and the product.
The GP components conform to the following standards:
*1
- UL1604
- UL60950 Third Edition
- CAN/CSA-C22.2 No.60950-00
GP2300-LG41-24V (UL Registration Model: 2980070-01)
GP2300-TC41-24V (UL Registration Model: 2980070-02)
GP2301-LG41-24V (UL Registration Model: 2980070-04)
GP2301-SC41-24V (UL Registration Model: 2980070-03)
GP2301-TC41-24V (UL Registration Model: 3180034-02)
Installation Precautions
If the GP is mounted so as to cool itself naturally, please mount it on a vertical panel.
Also, insure that the GP is mounted at least 100 mm away from any other adjacent
structures or machine parts. If these conditions are not met, the heat generated by the
GP's internal components may cause it to fail to meet UL standards.
UL1604 - Compliance and Handling Cautions
1. Power and input/output wiring must be in accordance with Class I, Division 2 wiring
methods - Article 501-4(b) of the National Electrical Code, NFPA 70 within the
United States, and in accordance with Section 18-152 of the Canadian Electrical
Code for units installed within Canada.
2. Suitable for use in Class I, Division 2, Groups A, B, C, and D, Hazardous Locations.
3. WARNING: Explosion hazard - substitution of components may impair compliance
4. WARNING: Explosion hazard - when in hazardous locations, turn the power OFF
5. WARNING: Explosion hazard - confirm that the power supply has been turned OFF
*1 GP2300-LG41-24V units with revision code "L" or later, GP2300-TC41-24V
units with revision code "J" or later, GP2301-LG41-24V units with revision
code "L" or later, and GP2301-SC41-24V units with revision code "K" or
later are all UL1604 compliant. See "Revision Information" in page 12 for
how to identify your unit's revision code.
GP-2300/2301 Series User Manual
Electrical Equipment for use in Class I and II,
Division 2, or Class III Hazardous (locations).
Safety of Information Technology Equipment
Safety of Information Technology Equipment
to Class I, Division 2.
before replacing or wiring modules.
before disconnecting equipment, or confirm that the
location is not subject to the risk of explosion.
Preface