Pro-face GP-4100 series Installation Manual

Hide thumbs Also See for GP-4100 series:

Advertisement

Quick Links

GP-4100 Series

Installation Guide

Please read the "Warning/Caution
Information" on the attached sheet
before using the product.
GP-4100 Series Connection Types
RS-232C type
RS-422/485 type
RS-485 (isolation) type
Ethernet type

Package Contents

(1) GP Unit (1)
(2) Installation Guide (1) <This Guide>
(3) Warning/Caution Information (1)
(4) Installation Gasket (1, attached to the GP unit)
(5) Installation Fasteners (Set of 2)
(6) COM I/F Connector (1)
(For RS-232C and RS-422/485 types)
(7) DC Power Supply Connector (1)
(For the Ethernet type and a portion of models
(Attached to unit)
*1 Not included with models that have the following
type of power connector.
GP4105G1D
GP4105W1D
GP4106G1D
GP4106W1D
GP4107G1D
GP4107W1D
GP4104G1D
GP4104W1D
*1
This unit has been carefully packed, with special
attention to quality. However, should you find any-
thing damaged or missing, please contact your local
GP distributor immediately.
About the Manual
This manual describes wiring and installation
procedures. For more detailed information, refer to
the manuals indicated below.
Manual
GP-4100 Series
Hardware
Manual
Device/
PLC Connection
Manual
Maintenance/
Troubleshooting
The manuals can be selected from the help menu of
GP-Pro EX or downloaded from Pro-face Home Page.
http://www.pro-face.com/otasuke/

Electrical Specifications

Input Voltage
Rated Voltage DC19.2 to 28.8V
Allowable
Voltage Drop
Power
Consumption
In-Rush
Current
)
Voltage
Endurance
Insulation
Resistance
*1 When power is not supplied to USB devices.
1
Contents
Specifications, dimensions,
accessories, system design, overseas
standards, and other details.
System configuration of connected
devices (PLCs and other devices),
communication settings examples,
connection wiring diagram, and
other details.
• Troubleshooting
Help for solving problems.
• Maintenance
Details on the GP unit's Offline Mode
URL
GP4104*
GP4106*
GP4105*
DC24V
3ms or less
6.0 W or
6.2 W or
less
less
2.7 W or
3.0 W or
*1
*1
less
less
30 A or less
AC1,000V, 20mA for 1 min (between
charging and FG terminals)
DC500V, 10MΩ or more (between
charging and FG terminals)
GP4107*
6.5 W or
less
3.4 W or
*1
less

Advertisement

Table of Contents
loading

Summary of Contents for Pro-face GP-4100 series

  • Page 1: Installation Guide

    GP4104W1D Details on the GP unit’s Offline Mode The manuals can be selected from the help menu of Package Contents GP-Pro EX or downloaded from Pro-face Home Page. (1) GP Unit (1) http://www.pro-face.com/otasuke/ (2) Installation Guide (1) <This Guide> (3) Warning/Caution Information (1)
  • Page 2: Part Names And Functions

    Part Names and Functions External Interfaces RS-232C type, RS-422/485 type • For instructions on how to connect to other devices, always refer to the "GP-Pro EX Device/ PLC Connection Manual". Serial Interface Rear (RS-422/485 type ) Right side RS-485 (isolation) type •...
  • Page 3: Installation Requirements

    Communications Cable Specifications RS-485 (isolation) type D-Sub 9-pin socket type connector Communications 0.14 to 1.5mm Cable Diameter (28 - 16 AWG) RS-485 (isolation) type Pin Connection Conductor Type Simple or Stranded Wire PIN # Signal Name Conductor [0.28in] LINE(+) Length RS(RTS) When inserting two wires into one terminal con- *2*3...
  • Page 4 GP unit. • It is strongly recommended that you use the instal- lation gasket, since it absorbs vibration in addition to repelling water. Bottom For the procedure for replacing the installation gas- ket, refer to “GP-4100 Series Hardware Manual”.
  • Page 5 Wiring the Power Cord No.1 • Tightening the screws with too much force can Power Cord Specifications damage the GP unit’s plastic case. • In order to guarantee water repelling effect the Use copper conductors only. necessary torque is 0.52N•m [4.60Lb•in]. Simple Wire: 0.75 to 1.5mm Power Cord Stranded Wire: 0.75 to 1mm...
  • Page 6: Wiring Cautions

    Wiring the Power Cord No.2 Wiring Cautions Power Cord Specifications Improving Noise/Surge Resistance • Use copper conductors only. • The GP unit’s power supply cord should not be bundled with or kept close to main circuit lines Power Cord 0.75 to 1.5mm (high voltage, high current), power lines, or input/ Diameter (18 - 16 AWG)
  • Page 7 Ca = 16 µF UL/c-UL Approval La = 10 µF 2. Selected Associated Nonincendive Field Wiring Apparatus shall satisfy the following: <Cautions> Be aware of the following items when building the Nonincendive Associated Field Nonincendive Field GP unit into an end-use product: Wiring Wiring Apparatus for •...
  • Page 8 Do you have any questions about difficulties with your GP? Please access our site anytime that you need help with a solution. http://www.pro-face.com/otasuke/ Note Please be aware that Digital Electronics Corpora- tion shall not be held liable by the user for any damages, losses, or third party claims arising from the uses of this product.