Closed or open switch means one of the following:
Blocking (A: Closed, B: Open)
"SG Ready" is active. The compressor in the heat
pump and additional heat is blocked.
Normal mode (A: Open, B: Open)
"SG Ready" is not active. No effect on the system.
Low price mode (A: Open, B: Closed)
"SG Ready" is active. The system focuses on costs
savings and can for example exploit a low tariff from
the electricity supplier or over-capacity from any own
power source (effect on the system can be adjusted
in the menu 4.1.5).
Overcapacity mode (A: Closed, B: Closed)
"SG Ready" is active. The system is permitted to run
at full capacity at over capacity (very low price) with
the electricity supplier (effect on the system is set-
table in menu 4.1.5).
(A = SG Ready A and B = SG Ready B )
• +Adjust
Using +Adjust, the installation communicates with
the underfloor heating's control centre* and adjusts
the heating curve and calculated supply temperature
according to the underfloor heating system's recon-
nection.
Activate the climate system you want +Adjust to affect
by highlighting the function and pressing the OK but-
ton.
*Support for +Adjust required
Caution
This accessory may require a software up-
date in your F370. The version can be
checked in the "Service info" menu 3.1.
Visit
nibeuplink.com
ware" tab to download the latest software
to your installation.
Caution
In systems with both underfloor heating and
radiators, NIBE ECS 40/41 should be used
for optimum operation.
External blocking of functions
An external switch function can be connected to F370
for blocking various functions. The switch must be po-
tential-free and a closed switch results in blocking.
NOTE
Blocking entails a risk of freezing.
Functions that can be blocked:
NIBE F370
and click on the "Soft-
• hot water (hot water production). Any hot water circu-
lation (HWC) remains in operation.
• heating (blocking of heating demand)
• internally controlled additional heat
• compressor
• tariff blocking (additional heat, compressor, heating
and hot water are disconnected)
Chapter 5 | Electrical connections