Caution
There must be a heating or hot water demand
to start the compressor.
NOTE
Do not quick start the compressor too many
times over a short period of time, as this could
damage the compressor and its surrounding
equipment.
MENU 5.9 - FLOOR DRYING FUNCTION
length of period 1 – 7
Setting range: 0 – 30 days
Factory setting, period 1 – 3, 5 – 7: 2 days
Factory setting, period 4: 3 days
temp. period 1 – 7
Setting range: 15 – 70 °C
Default value:
temp. period 1
temp. period 2
temp. period 3
temp. period 4
temp. period 5
temp. period 6
temp. period 7
Set the function for under floor drying here.
You can set up to seven period times with different
calculated flow temperatures. If less than seven periods
are to be used, set the remaining period times to 0 days.
Mark the active window to activate the underfloor drying
function. A counter at the bottom shows the number of
days the function has been active.
TIP
If operating mode "add. heat only" is to be used,
select it in menu 4.2.
TIP
It is possible to save a floor drying log that
shows when the concrete slab has reached
the correct temperature. See section
floor
drying" on page 56.
MENU 5.10 - CHANGE LOG
Read off any previous changes to the control system
here.
The date, time, ID no. (unique to particular setting) and
the new set value are shown for every change.
NIBE F370
Caution
The change log is saved at restart and remains
unchanged after factory setting.
5.12 - COUNTRY
Select here the country in which the product was in-
stalled. This allows access to country-specific settings
in your product.
Language settings can be made regardless of this selec-
tion.
Caution
This option locks after 24 hours, after restarting
the display and during program updating.
20 °C
30 °C
40 °C
45 C
40 °C
30 °C
20 °C
"Logging
Chapter 8 | Control - Menus
51