Start / Stop with 2 Constant Speeds

Set DIP switches to voltage signal positions
Motor starts by activating DI1 (11)
Two different constant speeds can be set
Constant speed 1 is set with parameter 1202
Constant speed 2 is set with parameter 1203
Constant speed 1 is selected with DI4 (14)
Constant speed 2 is selected with DI5 (15)
Start/Stop
Constant speed 1/2
14
DIP switches
AI1: 0- 10 V
AI2: 0- 10 V
X1
SCR
Screen control signal cable
1
AI1
+ Control signal 0 - 10V
2
AGND
-
3
+10V
+ Reference voltage 10 VDC
4
AI2
+ Pressure sensor 0 - 10V
5
-
AGND
6
Output frq 0 - 50Hz <=> 0 - 20mA
AO1
7
AGND
8
+24V
+ Auxiliary voltage 24 VDC
9
DCOM1
10
DI1
Start / Stop
11
DI2
12
Activate PID control
DI3
13
Select setpoint1 / setpoint2
DI4
14
Constant speed 1
DI5
Constant speed 2
15
DCOM2
16
RO1C
17
RO1A
18
RO1B
19
RO2C
20
RO2A
21
RO2B
22
Fault = 17-19
breaks
Running =
20 connected to 22