Internal Timer with Constant Speeds / PRV macro

This macro configures for applications such as a timed powered roof ventilator
(PRV) which alternates between two constant speeds (constant speed 1 and 2)
based on a built-in timer.
Momentarily activating digital input 3 (DI3) provides a boost function which operates
the motor. See group 36, Timer Functions, for more information on setting up timers.
mA
9902
1002
1103
1106
1201
1401
1601
1609
3415
3416
X1
Signal cable shield (screen)
1
SCR
External reference 0(2)...10 V or 0(4)...20 mA
2
AI1
+
Analog input circuit common
3
AGND
Reference voltage 10 VDC
4
10V
Not configured
5
AI2
Analog input circuit common
6
AGND
Output frequency: 0(4)...20 mA
7
AO1
mA
Output current: 0(4)...20 mA
8
AO2
Analog output circuit common
9
AGND
Auxiliary voltage output +24 VDC
10 24V
Auxiliary voltage output common
11 GND
Digital input common for all
12 DCOM
Timer enable: Activate to start/stop drive from timer
13 DI1
Run permissive: Deactivate to stop drive (P 1601)
14 DI2
Timer override: Activate to start drive
15 DI3
Safety interlock 1: Deactivate to stop drive (P 1608)
16 DI4
Safety interlock 2: Deactivate to stop drive (P 1609)
17 DI5
Not configured
18 DI6
19 RO1C
20 RO1A
21 RO1B
22 RO2C
23 RO2A
24 RO2B
25 RO3C
26 RO3A
27 RO3B
Parameters Changed Relative to HVAC Default
Parameter
9 (
APPLIC MACRO
INT TIMER CS
2
0 (
EXT
COMMANDS
NOT SEL
1
0 (
REF
SEL
KEYPAD
2
2 (
REF
SEL
AI
15 (
CONST SPEED SEL
TIMER
1
7 (
RELAY OUTPUT
STARTED
2 (
RUN ENABLE
DI
2
5 (
START ENABLE
DI
3
0105 (
SIGNAL
PARAM
3
-200.0%
SIGNAL
MIN
Relay output 1 (P 1401)
Default operation: Started =>19 connected to 21
Relay output 2 (P 1402)
Default operation: Running =>22 connected to 24
Relay output 3 (P 1403)
Default operation: Fault (-1) =>25 connected to 27
(Fault => 25 connected to 26)
Value
)
3417
)
3419
)
3420
2)
3421
1)
3601
)
3622
2)
3626
5)
4010
)
4110
TORQUE
J1
Jumper Settings
AI1: 0(4)
AI2: 0(4)
Parameter
3
200.0%
SIGNAL
MAX
3
4 (%)
OUTPUT
UNIT
3
-200.0%
OUTPUT
MIN
3
200.0%
OUTPUT
MAX
1 (
TIMERS ENABLE
DI
3 (
BOOST SEL
DI
1
31 (
TIMER
SRC
P
1 (
1)
SET POINT SEL
AI
1 (
1)
SET POINT SEL
AI
Application macros
1-59
ON
...
20 mA
...
20 mA
1
2
Value
1)
3)
1+2+3+4+
)
B

Advertisement

Table of Contents
loading

Table of Contents