I/O Configuration - ABB ACS 400V Instructions Manual

Low voltage ac drives
Table of Contents

Advertisement

I/O Configuration

The following diagram summarizes the I/O connection alternatives given by the ACS 400V.
Input signals
• Start/stop (DI1)
• Control signal 0 - 10 V(AI1)
• Actual value 0 - 10 V, eg. from
pressure sensor (AI2)
• Activate to select PID control
(DI2)
• Select setpoint1/setpoint2 (DI3)
• Constant speed 1 (DI4)
• Constant speed 2 (DI5)
DI configuration
NPN connected
(sink)
Figure 5 ACS 400V I/O connection.
Output signals
• Analogue output AO: Frequency
0 - 50 Hz <=> 0- 20 mA
• Relay output 1: Fault
-> 17 connected to 18
• Relay output 2: Running
-> 20 connected to 22
X1
1
SCR
2
AI1
3
AGND
4
+10V
5
AI2
6
AGND
7
AO1
8
AGND
9
+24V
10
DCOM1
11
DI1
12
DI2
13
DI3
14
DI4
15
DI5
16
DCOM2
17
RO1C
18
RO1A
19
RO1B
20
RO2C
21
RO2A
22
RO2B
DIP switches, set to
voltage signal positions
+24V
±0V
DI configuration PNP
connected (source)
with external
power supply
AI1: 0 - 10 V
AI2: 0 - 10 V
X1
1
SCR
2
AI1
3
AGND
4
+10V
5
AI2
6
AGND
7
AO1
8
AGND
9
+24V
10
DCOM1
11
DI1
12
DI2
13
DI3
14
DI4
15
DI5
16
DCOM2
17
RO1C
18
RO1A
19
RO1B
20
RO2C
21
RO2A
RO2B
22