Zone addressing with the RMZ operator units

7.2.1
RM... controllers
For the Synco 700 type RM... controllers, the zone addresses can be set with the
RMZ790 and RMZ791 operator units. The zone addresses can be set without a
commissioning tool, also referred to as "Easy configuration".
Access at the Password level
operating lines.
To set the zone address, use the following path to the "Room" operating page:
Main menu > Commissioning > Communication > Room
Turn the rotary knob to select the "Geogr zone (apartm)" line.
Room
Geogr. zone (ap.):
Time switch op:
TS slave (apart.):
Room
Geogr. zone (ap.):
TS slave (apart.):
Time switch op:
Turn the knob as required for access to setting mode.
Geographical zone (apartment)
1
1
└┴┴┴┴┴┴┴┴┴┴┴┴┴┴┴┴┘
Geographical zone (apartment)
----
1
└┴┴┴┴┴┴┴┴┴┴┴┴┴┴┴┴┘
In setting mode, set the zone address rotating the knob as required.
Geographical zone (apartment)
5
1
└┴┴┴┴┴┴┴┴┴┴┴┴┴┴┴┴┘
Basic documentation: Communication via the KNX bus
Communication via zone addresses
takes the user to the operating pages and
1
Autonom
1
----
----
Autonom
126
126
126
CE1P3127en