Geographical Zone (Apartment) - Siemens Synco 700 Series Basic Documentation

Communication via the knx bus
Hide thumbs Also See for Synco 700 Series:
Table of Contents

Advertisement

Definition
Geographical zone
RM...controllers
RM...B controllers
Note
Communication of the
room temperature
Building Technologies
HVAC Products
7.1.3

Geographical zone (apartment)

The term "Geographical zone (apartment)" is specified by KNX and implies a
building divided into geographical (physical) zones. However, in practice it is
related to the operating strategy, which is defined as follows:
• One "Geographical zone (apartment)" consists of a number of buildings or parts
of buildings which are grouped together from an operational point of view and
which obey the following criteria:
Same room operating mode
Same room temperature (setpoint, actual value).
Based on this definition, the "geographical zone (apartment)" might better be
referred to as an "operating zone".
The "geographical zone (apartment)" is used in conjunction with the RM...
controllers, the RXB/RXL room controllers and the QAW740 room unit.
Main menu > Commissioning > Communication > Room
Room
Geogr zone (ap.):
Time switch op:
TS slave (apart.):
Raum
Geogr zone (ap.):
TS slave (apart.):
Time switch op:
Geographical zone (apartment)
RM... default
1
RM... B default
----
Setting
1...126
The "Room" operating page and some other operating pages for the RM...
controllers (RMU7x0 and RMH760) are different from those for the RM...B
controllers (series B devices).
Communication of the room temperature from the QAW740 to an RM... controller
via "Geogr zone 5":
QAW740
Room temperature
Room unit
Geogr zone: 5
Basic documentation: Communication via the KNX bus
Communication via zone addresses
1
Autonom
1
----
----
Autonom
RM..
Room temperature
Controller
Geogr zone: 5
69/120
CE1P3127en
30.08.2007