Hide thumbs Also See for QAX910:

Advertisement

s
CE1N2707en
06.01.2009
Synco™ living
Central apartment unit
Series C
• Management of room control for one apartment including precontrol of
heating for 2 room groups
• Management of ventilation plant
• Management of air conditioners (e.g. split units)
• Selection of operating mode, timer and holidays / special day function for
the apartment
• Autonomous time switches and operating modes for 12 rooms
• Absence function (heating, cooling, ventilation, lights, blinds) with simula-
tion of presence (lights)
• Monitoring of windows and doors
• Summer operation with preselected valve position for cooling mode
• Display of meteorological data
• DHW heating with time switch and selection of operating mode
• Wireless communication with the devices of the Synco living,
GAMMA wave and Hager tebis TX ranges
• Switching groups with softkeys for the control of lights and blinds
• Choice of scenes for light and blind control
• Universal input and output
• Presentation of key data on Info pages
• Wireless (868 MHz, bidirectional) and wired connection for data transmis-
sion conforming to KNX standard
• Mains-powered AC 230 V
2
QAX910
Building Technologies
707

Advertisement

Table of Contents
loading

Summary of Contents for Siemens QAX910

  • Page 1 Synco™ living QAX910 Central apartment unit Series C • Management of room control for one apartment including precontrol of heating for 2 room groups • Management of ventilation plant • Management of air conditioners (e.g. split units) • Selection of operating mode, timer and holidays / special day function for the apartment •...
  • Page 2: Equipment Combinations

    • Remote access via Siemens OZW77x central communication units Equipment combinations The central apartment unit can be used in connection with the following RF prod- ucts of the Siemens Synco living system and those of other suppliers of wireless KNX products: Description Product No.
  • Page 3 In addition, it provides control of air conditioners (split units), light and blind actua- tors and monitors light actuators, door and window contacts as well as smoke de- tectors. The QAX910 also serves as an operator and display unit for the apartment. 3 / 16 Siemens...
  • Page 4: Antilime Function

    RRV912 / RRV918 heating circuit controllers or the RRV934 multi-controller. Antilime function The QAX910 can trigger the antilime function at regular intervals, aimed at prevent- ing valve plugs and pump impellers from seizing during longer off periods. The function ensures that the valve actuators will travel to the fully open and then to the fully closed position and that the pumps will be activated for short periods of time (valve kick).
  • Page 5 0% or 100% and the SSA955 radiator control actuators will be driven to the preselected valve positions. DHW charging / The QAX910 provides DHW control with the help of a specific DHW time switch. DHW control DHW heating is either enabled or disabled based on the temperature acquired by the DHW temperature sensor connected to the QAX910 or an RRV912 / RRV918 / RRV934.
  • Page 6: Light Control

    In addition to manual adjustments, the blinds can be set via the internal time switch (time switch can "Always“ be processed or "Only if absent“), scenes or events (e.g. twilight, absence). Suited are Siemens GAMMA wave and Hager tebis blind actuators, as well as KNX TP1 blind actuators. 6 / 16...
  • Page 7 The central apartment unit has 8 fault inputs and 2 fault outputs which can be used Fault inputs / fault outputs via the universal input / output of the QAX910 (locally), the universal inputs / out- puts of the RRV912 / RRV918 heating circuit controllers or the RRV934 multi- controller.
  • Page 8 The RF adapter plugs can be switched via external buttons (GAMMA wave), hand- held transmitters (GAMMA wave) or directly with the plug’s own function button. 8 / 16 Siemens Central apartment unit QAX910 CE1N2707en Building Technologies 06.01.2009...
  • Page 9: Error Messages

    When power is restored, the central apartment unit and its components will resume normal control operation. To facilitate fault tracing, the QAX910 delivers detailed error messages. Error messages They are output as clear-text messages, thus simplifying the interpretation of mes- sages by the user or the heating engineer.
  • Page 10 Q1 - Q3 3-stage step selector of ventilation plant Exhaust air Indoor air quality sensor, DC 0...10 V Outside air Humidity sensor, DC 0...10 V Supply air Extract air 10 / 16 Siemens Central apartment unit QAX910 CE1N2707en Building Technologies 06.01.2009...
  • Page 11: Operating Elements

    Universal pair of softkeys 1 - 4 These buttons are used to trigger the switching group functions (e.g. for switching or dimming the lights) defined during commissioning, or to retrieve predefined info displays. 11 / 16 Siemens Central apartment unit QAX910 CE1N2707en Building Technologies 06.01.2009...
  • Page 12: Mounting Location

    • The central apartment unit is designed for wall mounting Mounting location • Mount the QAX910 in a space that is easily accessible (e.g. in the living room or in the hall). The mounting height above the floor should be chosen such that the unit is easily accessible.
  • Page 13: Warranty

    Synco living system. When using the QAX910 central apartment unit together with devices of other manufacture not specifically mentioned, correct functioning must be ensured by the user. In that case, Siemens does not provide any service or warranty. 13 / 16 Siemens...
  • Page 14 Degree of pollution 2 to EN 60730 Refer to “Dimensions“ Dimensions Unit complete with enclosures 0.857 kg Weight Plastic ASA+PC Housing material White NCS S 0502-G Housing color 14 / 16 Siemens Central apartment unit QAX910 CE1N2707en Building Technologies 06.01.2009...
  • Page 15: Connection Terminals

    Ground for universal input Universal input Connection diagram Q 13 Central apartment unit QAX910 Universal input, for temperature measurement / digital input Universal potential-free relay output for mains or low-voltage Live conductor AC 230 V Neutral conductor AC 230 V...
  • Page 16 Dimensions Dimensions in mm Central apartment unit Base 16 / 16 © 2007-2009 Siemens Switzerland Ltd Subject to change Siemens Central apartment unit QAX910 CE1N2707en Building Technologies 06.01.2009...