4.1
Recording Status Detailed Information Screen
This section shows the screen for displaying detailed information on the recording function status.
Window
Click the [...] button in the "Detail" column.
(2)
Displayed items
Item
(1) Monitoring status
[Start Monitoring]/[Stop Monitoring] button
(2) Setting tab
Recording Status Detailed
Information
Recording Files Saving Information
(1)
*1
Recording Startup Trigger Count
Invalid Recording Startup Trigger
*1
Count
*1
File Saving Trigger Count
*1
Invalid File Saving Trigger Count
*1
Recording File Saving Count
*1
Cumulative Size (Average) [KB]
*1
Sampling Interval (Average) [ms]
*1
Accumulated Data
*2
Batch Saving
*1,*3,*4
Path Saved at Last
Description
The monitoring status is displayed.
Click this to start or stop monitoring.
Select the tab of a recording setting to display its detailed information.
The tab of a recording setting selected in the "Recording Monitor" screen is
selected by default.
The number of times that a recording startup trigger was detected to have
been satisfied is stored.
(Value to be stored: 0 to 65535)
The number of invalid recording startup triggers among the recording startup
triggers detected to have been satisfied is stored.
(Value to be stored: 0 to 65535)
The number of times that a file saving trigger was detected to have been
satisfied is stored.
(Value to be stored: 0 to 65535)
The number of invalid file saving triggers among the file saving triggers
detected to have been satisfied is stored.
(Value to be stored: 0 to 65535)
The number of times that a recording file was saved (total of successful and
failed ones) is stored.
(Value to be stored: 0 to 65535)
The average size of devices and labels accumulated at a time is stored.
The average value of device and label sampling intervals is stored.
When selecting "Trigger Instruction" for the sampling method, the execution
interval of the DATATRG instruction is the sampling interval.
When data is accumulated once, "Data Exists" is displayed.
If using a recording startup trigger, data is not accumulated before the trigger
is satisfied.
Depending on the timings of data accumulation and a recording startup
trigger, accumulated data may not be included in a saving period and may not
be saved to a recording file.
Whether the recording buffer batch saving mode is enabled is displayed.
(Page 39 Recording buffer batch saving mode)
• OFF: Disabled
• ON: Enabled
The mode can be switched by right-clicking the cell and selecting [ON] or
[OFF].
The path to a folder for saving a last saved recording file is stored.