Ul Compliance Requirements; Ul1610 - ICT Protege PRT-PX8-DIN Installation Manual

Din rail 8 pgm output expander
Hide thumbs Also See for Protege PRT-PX8-DIN:
Table of Contents

Advertisement

In the ArmorIP Internet Monitoring Software the Poll Time must be set to 40 seconds and the Grace Time
must be set to 20 seconds. Refer to the section
Application User Manual (227-5500-000).
Central Station Signal Receiver
The maximum number of signal transmitting units connected to any transmission channel shall conform to
the manufacturer's recommendations. The ArmorIP Receiver supports up to 10000 simultaneous
connections.
Refer to the section
(227-5510-000) for further details.
Number of attempts
In the event of unsuccessful communication, a digital alarm communicator transmitter shall make a
minimum of 5 and a maximum of 10 attempts. Where the maximum number of attempts to complete the
sequence is reached, an indication of the failure shall be made at the premises.
In the Protege System, the reporting service selected as Contact ID must have the number of attempts
programmed to 5 attempts. The Dialing Attempts option must be programmed. Refer to the section
Contact ID | Settings
Check-In Time
DACT communication channel check-in time is not to exceed 24 hrs.
Trouble Input Service Test Report
The Test Report Time must be programmed. Refer to the section
ProtegeGX Operator Reference Manual (227-1500-000).
The Generate Input Restore on Test Input option must be enabled. Refer to the section
Options
in the ProtegeGX Operator Reference Manual (227-1500-000).
The Test Report Time is Periodic option must be enabled. Refer to the section
the ProtegeGX Operator Reference Manual (227-1500-000).
Ethernet Connections
All Ethernet network connections shall be installed within the same room as the equipment.
Power Supply Mains Power Connection
If a flexible cord is used to connect to line voltage, strain relief must be provided for the cord inside the
enclosure or at the knockout.
The Power Supply is not intended to be mounted on the exterior of vault, safe, or stockroom.
Arming Signal
A bell or visual indicator used as an arming acknowledgement signal must be listed to a ULC security,
signaling or fire standard. If intended to be mounted outside, it must be rated for outdoor use.
Keypad Wiring
The RS-485 connection to the keypad must be wired such that the shorts and other faults on the RS-485
line connection of the keypad will not cause the controller to malfunction.
Fire Zones
Fire zones shall be separated from burglar zones through area partitioning.
NOTE: Any available dry relay contact on the PRT-CTRL-DIN or PRT-PX8-DIN may be used for the FACP
system, provided the selected output is programmed as the Report OK PGM.
 

15.3 UL Compliance Requirements

UL1610

A local alarm sounding device, alarm housing, and control unit shall comply with the mercantile
requirements in the Standard for Police Station Connected Burglar Alarm Units and Systems, UL365.
A bell or visual indicator used as an arming acknowledgement signal must be listed to a UL security,
signaling or fire standard. If intended to be mounted outside, it must be rated for outdoor use.
Exit and entry delay must not exceed 60 seconds. To program the entry and exit delay time, refer to the
section
Areas | Configuration
All Ethernet network connections shall be installed within the same room as the equipment.
Protege DIN Rail 8 PGM Output Expander
Internet Connections Requirements
in theProtegeGX Operator Reference Manual (227-1500-000).
in the ProtegeGX Operator Reference Manual (227-1500-000).
| Installation Manual
Poll/Grace Time
in the ArmorIP Internet Monitoring
in the ArmorIP Receiver Installation Manual
Controllers | Configuration
in the
Controller |
Controller | Options
in
27

Advertisement

Table of Contents
loading

Table of Contents