A local alarm sounding device, alarm housing, and control unit shall comply with the mercantile
requirements in the Standard for Police Station Connected Burglar Alarm Units and Systems, UL365.
A bell or visual indicator used as an arming acknowledgement signal must be listed to a UL security,
signaling or fire standard. If intended to be mounted outside, it must be rated for outdoor use.
Exit and entry delay must not exceed 60 seconds. To program the entry and exit delay time, refer to the
section
Areas | Configuration
All ethernet network connections shall be installed within the same room as the equipment.
Signals between the premises control unit and the receiving equipment, when not carried by wireless
means, shall be protected by the following method:
-
Onboard modem telco connection must be dedicated to the Protege controller.
-
Ethernet connection to the Internet Service Provider (ISP) with a fixed IP Address must be dedicated to
the Protege controller.
To comply with the dual signal line transmission system requirement,
modem and IP reporting) must be enabled. Signals shall be sent simultaneously to both, Report IP Service
and Contact ID Reporting Service.
The Report IP and Contact ID services must be programmed and enabled within the Protege system. The
following options are required:
-
The Contact ID Reporting Service must be enabled and the Service Mode must be configured to start
with the operating system.
-
Refer to the section
-
The Report IP Service must be enabled as the primary communication channel, the Service Mode must
be configured to start with the operating system, and the Reporting Protocol must be set to ArmorIP.
-
Refer to the section
When more than one means of signal transmission is used, loss of communication with the receiving system
shall be annunciated at the receiver within 200 seconds. If a fault is detected on any of the signal
transmission means, at least one of the signal transmission channels shall send a signal to the central-
station to report the fault within 200 seconds.
The Report IP and Contact ID services must be programmed and enabled within the Protege system.
The Protege controller is compatible with the ArmorIP Internet Monitoring Receiver. Poll Time must be set
to 40 seconds and the Grace Time must be set to 20 seconds.
In the Protege system, the reporting service must be configured to 40 seconds. The following options are
required for the service selected as Report IP type:
-
The Poll Time must be programmed to 40 seconds. Refer to the
Operator Reference Manual
-
The Contact ID Reporting Service must be enabled and the Service Mode must be configured to start
with the operating system.
-
Refer to the section
-
The Report IP Service must be enabled as the primary communication channel, the Service Mode must
be configured to start with the operating system, and the Reporting Protocol must be set to ArmorIP.
-
Refer to the section
-
The Trouble Input Area must be armed in 24h mode. Refer to the section
Input Types
in the Operator Reference Manual.
In the event of unsuccessful communication, a digital alarm communicator transmitter shall make a minimum
of 5 and a maximum of 10 attempts. Where the maximum number of attempts to complete the sequence is
reached, an indication of the failure shall be made at the premises.
In the Protege system, the reporting service selected as Contact ID must have the number of attempts
programmed to 5 attempts. The following options are required:
PRT-ZX16-DIN | Protege DIN Rail 16 Input Expander | Installation Manual
in the Operator Reference Manual.
Contact ID
in the Operator Reference Manual.
Report IP
in the Operator Reference Manual.
Contact ID
in the Operator Reference Manual
Report IP
in the Operator Reference Manual.
both
transmission lines (onboard
Report IP | General
section in the
Trouble Inputs | Areas and
31