15 UL and ULC Installation Requirements

Only UL / ULC listed compatible products are intended to be connected to a UL / ULC listed control system.
 

15.1 UL/ULC Installation Cabinet Options

UL/ULC Central Station Fire Monitoring, Central Station Alarm Installations
Cabinet Model
EN-DIN-24-ATTACK
Electronic Access Control System Installations
All cabinet installations of this type must be located inside the Protected Area. Not to be mounted on
UL
ULC
the exterior of a vault, safe or stockroom
Cabinet Model
EN-DIN-12
EN-DIN-31
EN-DIN-24
EN-DIN-24-ATTACK
All cabinet internal covers and lid/doors must be connected to the cabinets main ground point for
electrical safety and static discharge protection.
 

15.2 ULC Compliance Requirements

CAN/ULC-S304-06

Auto Arming
Control units that support auto arming shall provide an audible signal throughout the protected area not less
than 10 min prior to the auto arming taking place. The control unit shall allow authorized users to cancel the
auto arming sequence and transmit such cancelation to the signal receiving center with the identification of
the authorized user that canceled the action.
The following options must be enabled in the Protege System when using the Auto Arming feature. When
the defer warning time is programmed to 10 minutes, the Output group will be activated 10 minutes before
the system performs the Auto Arming in the associated Area.
The Defer Output or Output Group must be programmed. Refer to the section
ProtegeGX Operator Reference Manual (227-1500-000) for programming instructions.
The Defer Warning Time must be programmed to not less than 10 minutes. Refer to the section
| Configuration
in the ProtegeGX Operator Reference Manual (227-1500-000).
The Defer Automatic Arming arming option must be enabled. Refer to the section
the ProtegeGX Operator Reference Manual (227-1500-000).
Arming Signal
Protege DIN Rail 8 PGM Output Expander
Manufacturer
ICT
Manufacturer
ICT
ICT
ICT
ICT
| Installation Manual
UL/ULC Installation Listings
UL1610, UL1635, ULC-S304, ULC-S559
UL/ULC Installation Listings
UL294, CAN/ULC-S319
UL294, CAN/ULC-S319
UL294, CAN/ULC-S319
UL294, CAN/ULC-S319
Areas | Outputs