Lowara E6 PWM Series Installation And Operating Instructions Manual page 5

For heating and cooling application

Advertisement

5.
Characteristic Curve (see figure 2)
6.
Installation Advice
The installation of a stop valve upstream and downstream of the pump
is recommended so the pump can be replaced at a later time without
the need to completely drain the system.
7.
Installation
The unit may not be installed in areas where there is a
danger of explosion and may not be used to pump
flammable liquids.
Figure 3: Only install in dry, frost-proof rooms in one of the permitted
fitting positions.
The use of thermal insulation shells, available from the manufacturer,
is recommended when a thermal insulation of the pump is required.
When using other materials, leave the motor housing uninsulated,
otherwise the electronics may overheat and the pump may
automatically switch off.
Screw connections for installing the pump in the system are not
included in the scope of delivery. Use new gaskets (included in the
scope of delivery) when installing the pump.
The customer must take appropriate isolation measures and provide
appropriate acoustic insulation to reduce possible noise transfer.
7.1
Electrical connection (see figure 6)
The unit may only be connected by an authorized
electrician. The pump is equipped with a factory
installed cable.
The PWM wire must be connected to the controller with
the right polarity mentioned. ( see figure 6 )
The pump requires a separate circuit breaker installed
$77(17,21
on the phase with a rated value of 10A. The socket must
be positioned in such way that no water can drip onto it
even in the event of damage to the piping.