5.2.

TERMINAL CONNECTORS INTRINSICALLY SAFE APPLICATIONS:

Terminal connectors F030-A-OT-(PC / PD / PL / PX)-XI-(ZB):
SENSOR SIGNAL
ANALOG INPUT
TYPE: A (0)4-20mA
1
2
I
Fig. 16: Overview terminal connectors XI - Intrinsically Safe applications.
Remarks power supply options:
Type PC: offers - additional to type PX - an internal Intrinsically Safe lithium battery. This ATEX
certified battery (FW-LiBATT-xxx) may be changed in hazardous area.
Type PD: offers - additional to type PX - a sensor supply terminal (terminal 6) which offers the same
voltage as connected to terminal 5 (internally linked).
Type PX: as standard, all intrinsically product are supplied with terminal 4 and 5 to power the
product externally.
Type PL: the unit will be powered from the 4-20mA input signal. Terminal 4-6 are not available.
5.3.

CONFIGURATION EXAMPLES INTRINSICALLY SAFE APPLICATIONS:

Configuration example no. 1
Configuration example IIA - IIB and IIC application - F030-A-OT-PX-XI-ZB
TERMINAL CONNECTORS
F0-series
Supply backlight
Common ground
Common ground
Main supply
Common ground
Signal
Common ground
*Sensor supply voltage for analog flowmeter type A / U: not available in this example.
Please note: type PX may be used in combination with the battery (type PC). PX will power the unit; the battery will be disabled automatically till power is disconnected.
POWER SUPPLY
SENSOR
UNIT
SUPPLY
TYPE: PD / PX
TYPE: PD
4
5
6
+
+
Backlight option: type ZB
Intrinsically Safe apparatus
Control output type OT: passive transistor
Power supply type PX: 8-30V DC
I.S. flowmeter input - type A: (0)4-20mA
Fig. 17: Configuration example Intrinsically Safe.
HF030AEN_v0403_03 Atex_IECEx_CSA_FM
PULSE
POWER SUPPLY
OUTPUT
BACKLIGHT
TYPE: OT
OPTION: ZB
7
8
9
R1
R1
HAZARDOUS AREA
SAFE AREA
Uo
= max. 30 V
Io
= max. 200 mA
Po
= max. 0,75 W
= max. 30 V
Uo
= max. 200 mA
Io
= max. 1,2 W
Po
= max. 30 V
Uo
= max. 200 mA
Io
= max. 1,2 W
Po
= max. 30 V
Uo
= max. 150 mA
Io
Po
= max. 0,92 W
Note: above values are safety values.
Consult the technical specification for operational values.
10
+
Power supply
For example
MTL5025
Power supply or
switch interface
For example
MTL5025
MTL5011B
e.g. relay
Power supply
For example
MTL5025
Power supply
For example
MTL5025