Fluidwell F074-A Manual

Fluidwell F074-A Manual

Level/pump controller
Hide thumbs Also See for F074-A:

Advertisement

Quick Links

F074-A
LEVEL / PUMP CONTROLLER
Signal input sensor: (0)4-20mA.
Output: one control output.
Options: Intrinsically Safe.
F-Series - Field mounted indicators for safe and hazardous areas. More info: www.fluidwell.com/fseries

Advertisement

Table of Contents
loading

Summary of Contents for Fluidwell F074-A

  • Page 1 F074-A LEVEL / PUMP CONTROLLER Signal input sensor: (0)4-20mA. Output: one control output. Options: Intrinsically Safe. F-Series - Field mounted indicators for safe and hazardous areas. More info: www.fluidwell.com/fseries...
  • Page 2: Safety Instructions

     This unit must be installed in accordance with the EMC guidelines (Electro Magnetic Compatibility).  Do connect a proper grounding to the aluminum casing as indicated if the F074-A has been supplied with the 115-230V AC power-supply type PM. The green / yellow wire between the back-casing and removable terminal-block may never be removed.
  • Page 3: About The Operation Manual

    This operation manual describes the standard unit as well as most of the options available. For additional information, please contact your supplier. A hazardous situation may occur if the F074-A is not used for the purpose it was designed for or is used incorrectly. Please carefully note the information in this operating manual indicated by the pictograms: A "warning"...
  • Page 4: Table Of Contents

    Disposal ..............................2 Safety rules and precautionary measures ....................... 2 About the operation manual ..........................3 Contents manual .............................. 4 1.1. System description of the F074-A ..................5 Operational ..........................6 2.1. General ..........................6 2.2. Control panel .......................... 6 2.3.
  • Page 5: System Description Of The F074-A

    Fig. 1: Typical application for the F074-A. Configuration of the unit The F074-A has been designed to be implemented in many types of applications. For that reason, a SETUP-level is available to configure your F074-A according to your specific requirements.
  • Page 6: Operational

     Take careful notice of the " Safety rules, instructions and precautionary measures " in the front of this manual. This chapter describes the daily use of the F074-A. This instruction is meant for users / operators. 2.2. CONTROL PANEL The following keys are available: Fig.
  • Page 7: Operator Information And Functions

     Control output The function of the F074-A, fill up or pump out, is determined at configuration level, not at Operator level. If the output signal is switched on, the text “CONTROL ON” is displayed.
  • Page 8 Page 8 SET-UP READY PROGRAM ALARM LOW BATTERY Fig. 4: Example of display information during programming minimum level. When data is altered but ENTER has not been pressed yet, then the alteration can still be cancelled by waiting for 20 seconds or by pressing ENTER during three seconds: the former value will be reinstated.
  • Page 9: Configuration

    Operating Manual before carrying out its instructions.  The F074-A may only be operated by personnel who are authorized and trained by the operator of the facility. All instructions in this manual are to be observed.
  • Page 10 Page 10 Matrix structure SETUP-level: SCROLLING THROUGH SETUP-LEVEL Selection of function-group and function: SETUP is divided into several function groups and functions. Each function has a unique number, which is displayed below the word "SETUP" at the bottom of the display. The number is a combination of two figures. The first figure indicates the function-group and the second figure the sub-function.
  • Page 11 Page 11 To change or select a value: To change a value, use  to select the digits and  to increase that value. If the new value is invalid, the increase sign or decrease-sign will be displayed while you are programming.
  • Page 12: Overview Functions Setup Level

    CUT-OFF 0.0 - 99.9% CALIBRATE LOW default - calibrate - calibrate set CALIBRATE HIGH default - calibrate - calibrate set OTHERS TYPE / MODEL F074-A SOFTWARE VERSION 03.03.xx SERIAL NO. xxxxxxx PASS CODE 0000 - 9999 TAGNUMBER 0000000 - 9999999...
  • Page 13: Explanation Of Setup-Functions

    Page 13 3.2.3. EXPLANATION OF SETUP-FUNCTIONS 1 - LEVEL SETUP - 11 determines the measurement unit for the displayed level. MEASUREMENT UNIT The following units can be selected: L - m3 - kg - lb. - GAL - USGAL - bbl - _ (no unit). Alteration of the measurement unit will have consequences for operator and SETUP-level values.
  • Page 14: Height

    Page 14 2 - HEIGHT If desired the height of the level column can be calculated and displayed. SETUP - 21 determines the measurement unit for height. MEASUREMENT UNIT The following units can be selected: mm - cm - m - mtr - inch - ft - mmwk - mmwc - cmwk - cmwc mwk - mwc - inwc - ftwc - mbar - bar - psi - no unit.
  • Page 15: Control

    Page 15 3 - CONTROL With these settings, the function of the transistor / relay output terminals is determined. HIGH ON: in this case, the control output will be switched-on at the FUNCTION high level and switched-off at the low level. To be used for “pump out”...
  • Page 16: Power Management

    When used with the internal battery option, the user can expect reliable measurement over a long period of time. The F074-A has several smart power management functions to extend the battery life time significantly. Two of these functions can be set:...
  • Page 17: Sensor

    The analog output signal of a sensor does mirror the actual level. This FILTER signal is measured several times a second by the F074-A. The value measured is a "snap-shot" of the real level as it will be fluctuating. With the help of this digital filter a stable and accurate reading can be obtained while the filter level can be set to a desired value.
  • Page 18: Others

    For support and maintenance it is important to have information about the TYPE OF MODEL characteristics of the F074-A. Your supplier will ask for this information in the case of a serious breakdown or to assess the suitability of your model for upgrade considerations.
  • Page 19: Installation

    Operating Manual before carrying out its instructions.  The F074-A may only be operated by personnel who are authorized and trained by the operator of the facility. All instructions in this manual are to be observed.
  • Page 20: Dimensions- Enclosure

    Page 20 4.3. DIMENSIONS- ENCLOSURE Aluminum enclosures: 75 mm (2.95") 112 mm (4.40") 130 mm (5.12") 12mm 12mm 30mm 30mm 24mm 24mm M20 x 1,5 6 x M12 36mm 36mm 30mm 30mm M16 x 1,5 M16 x 1,5 1/2"NPT M20 x 1,5 0.12"...
  • Page 21 Page 21 GRP enclosures: 75 mm (2.95") 112 mm (4.40") 130 mm (5.12") HK back box: (flat bottom) 75 mm (2.95") 118 mm (4.65”) 25mm 25mm D=20mm D=20mm 12mm 12mm 30mm 30mm 24mm 24mm D=12mm D=16mm D=16mm D=20mm 36mm 36mm 0.12”...
  • Page 22: Installing The Hardware

     This unit must be installed in accordance with the EMC guidelines (Electro Magnetic Compatibility).  Do ground the aluminum casing properly as indicated, if the F074-A has been supplied with the 115-230V AC power-supply type PM. The green / yellow wire between the back- casing and removable terminal-block may never be removed.
  • Page 23: Terminal Connectors With Power Supply - Type : Pb / Pd / Pl / Px

    REMARKS: TERMINAL CONNECTORS: Terminals 1-2; Sensor input – type A: The F074-A requires a (0)4-20mA sensor signal which will be processed 4 times a second with a 16 bits accuracy. The input is not isolated. The screen of the signal wire must be connected to the common ground terminal...
  • Page 24 Page 24 Terminal 4-5: POWER SUPPLY UNIT - type PD / PX: To power the unit an internal battery can be used (type PB) and / or an external DC power supply of 8-30V DC (type PX) or 16-30V DC (type PD). Connect the "-"...
  • Page 25: Terminal Connectors With Power Supply - Type : Pf / Pm

    PF / PM OA-OR-OT ANALOG (0)4-20mA Fig. 10: Overview of terminal connectors F074-A-(PF-PM) and options. SENSOR SUPPLY Type PF-PM: Sensor supply: 8.2V, 12V or 24 V: With this option, a real power supply for the sensor is available. The sensor can be powered with 8.2, 12 or 24 V DC (max.
  • Page 26 Page 26 REMARKS: TERMINAL CONNECTORS: Terminal GND- 01- 02; POWER SUPPLY only available with type PF / PM: erminal PTION SENSOR SUPPLY PF 24V AC ± 10% 8.2, 12, 24V max. 400mA@24V DC PF 24V DC ± 10% 8.2, 12, 24V max. 400mA@24V DC PM 115-230V AC ±...
  • Page 27 Page 27 Terminals 5-7; Sensor input: The F074-A requires a (0)4-20mA sensor signal which will be processed 4 times a second with a 16 bits accuracy. The input is not isolated. The screen of the signal wire must be connected to the common ground terminal 5.
  • Page 28: Intrinsically Safe Applications

    Safety Instructions  Certificates, safety values, control drawing and declaration of compliance can be found in the document named: “Fluidwell F0..-A-XI - Documentation for Intrinsic Safety”.  For installation under ATEX directive: this intrinsically safe device must be installed in accordance with the Atex directive 94/9/EC and the product certificate KEMA 05ATEX1168 X.
  • Page 29 FWCD-0001. Tamb CSA Certificate nr: CSA.08.2059461 – FM Project ID: 3033306 -40°C ... +70°C Made in Veghel, The Netherlands by Fluidwell bv -40°F ... +158°F KEMA 05ATEX1168 X Battery powered applications: II 1 G Ex ia IIC T4 Replace with certified II 1 D Ex iaD 20 IP 65 / 67 T 100°C...
  • Page 30: Terminal Connectors Intrinsically Safe Applications

    Type PX: as standard, all intrinsically product are supplied with terminal 4 and 5 to power the product externally. 5.3. CONFIGURATION EXAMPLES INTRINSICALLY SAFE APPLICATIONS: Configuration example no. 1 Configuration example IIA - IIB and IIC application - F074-A-OT-PX-XI-ZB HAZARDOUS AREA SAFE AREA TERMINAL CONNECTORS F0-series = max.
  • Page 31 Page 31 Configuration example no. 2 Configuration example IIA - IIB and IIC application - F074-A-OT-PD-XI-ZB HAZARDOUS AREA SAFE AREA TERMINAL CONNECTORS F0-series = max. 30 V Power supply Supply backlight = max. 200 mA Backlight option: type ZB For example = max.
  • Page 32: Battery Replacement Instructions

    Page 32 5.4. BATTERY REPLACEMENT INSTRUCTIONS FW-LiBAT-001 - INST001 Fig. 19: Battery replacement instructions Intrinsically Safe Battery. HF074AEN_v0403_04 Atex_IECEx_CSA_FM...
  • Page 33: Maintenance

    Operating Manual before carrying out its instructions.  The F074-A may only be operated by personnel who are authorized and trained by the operator of the facility. All instructions in this manual are to be observed.
  • Page 34: Appendix A: Technical Specification

    Page 34 APPENDIX A: TECHNICAL SPECIFICATION GENERAL Display Type High intensity reflective numeric and alphanumeric LCD, UV-resistant. Digits Seven 17mm (0.67") and eleven 8mm (0.31"). Various symbols and measuring units. Refresh rate User definable: 8 times/sec - 30 secs. Type ZB (option) Bi-color configurable LED-backlight - green, amber.
  • Page 35 Page 35 Sensor excitation Type PB / PC / PL / PX Sensor supply not available. Type PD As connected power supply voltage (internally linked) Type PF / PM Sensor supply voltage 8.2, 12 and 24V DC - max. 400mA@24V DC Terminal connections Type: Removable plug-in terminal strip.
  • Page 36 Page 36 OPERATIONAL Operator functions Displayed functions • level. • height or percentage (or no indication). • high and low control level value. • control value’s can be entered (this function can be disabled). Level Digits 6 digits. Units L, m3, GAL, USGAL, KG, lb, bbl, no unit. Decimals 0 - 1 - 2 or 3.
  • Page 37: Appendix B: Problem Solving

    Page 37 APPENDIX B: PROBLEM SOLVING In this appendix, several problems are included that can occur when the F074-A is going to be installed or while it is in operation. Level displays "0 / zero" while a higher signal is available: Check: ...
  • Page 38: Index Of This Manual

    Page 38 INDEX OF THIS MANUAL actual settings level alarm 8, 37 decimals 13, 14 backlight enter control values color measuring unit density Span battery life time 15, 16, 33 Span Battery replacement loop powered configuration low current contents low-battery control main-function delay time output...
  • Page 39: List Of Figures In This Manual

    Fig. 8: Grounding aluminum enclosure with option PM 115-230V AC..........22 Fig. 9: Overview of terminal connectors F074-A-(PB / PD / PL / PX) and options......23 Fig. 10: Overview of terminal connectors F074-A-(PF-PM) and options........... 25 Fig.
  • Page 40 74 pass code 0000 75 tagnumber 0000000 Fluidwell bv HF074AEN_v0403_04 Atex_IECEx_CSA_FM PO box 6 Voltaweg 23 Website: www.fluidwell.com 5460 AA Veghel 5466 AZ Veghel Find your nearest representative: www.fluidwell.com/representatives The Netherlands The Netherlands Copyright Fluidwell bv - 2012 - HF110AEN_v0501_03...