F074-A
LEVEL / PUMP CONTROLLER
Signal input sensor: (0)4-20mA
Output: one control output
Options: Intrinsically Safe
F-Series - Field mounted indicators for safe and hazardous areas.
More info: www.fluidwell.com/fseries

Advertisement

Table of Contents
loading

Summary of Contents for Fluidwell F074-A

  • Page 1 F074-A LEVEL / PUMP CONTROLLER Signal input sensor: (0)4-20mA Output: one control output Options: Intrinsically Safe F-Series - Field mounted indicators for safe and hazardous areas. More info: www.fluidwell.com/fseries...
  • Page 2: Safety Instructions

    The F074-A must be installed in accordance with the EMC guidelines (Electro Magnetic Compatibility). • Connect a proper grounding to the metal enclosure as indicated if the F074-A has an incoming power or signal line which carries a hazardous live voltage. The Protective Earth (PE) wire may never be disconnected or removed.
  • Page 3: About The Manual

    This operation manual describes the standard F074-A as well as most of the options available. For additional information, please contact your supplier. A hazardous situation may occur if the F074-A is not used for the purpose it was designed for or is used incorrectly. Please carefully note the information in this operating manual indicated by the pictograms: A "warning !"...
  • Page 4: Table Of Contents

    ABOUT THE MANUAL ........................3 WARRANTY AND TECHNICAL SUPPORT ..................3 CONTENTS MANUAL ......................... 4 INTRODUCTION ........................6 System description of the F074-A .................... 6 OPERATIONAL ........................7 General information ......................... 7 Control panel ..........................7 Operator information and functions ..................7 CONFIGURATION ........................
  • Page 5 5.3.2 Terminal 6 - Type PD: Sensor supply ................... 37 Configuration examples Intrinsically Safe applications ............38 5.4.1 F074-A-OT-PX-XI-ZB - Ex ia IIC/IIIC ..................38 5.4.2 F074-A-OT-PD-XI-ZB - Ex ia IIC/IIIC ..................38 5.4.3 F074-A-OT-PL-XI-ZB - Ex ia IIC/IIIC ..................39 MAINTENANCE ........................
  • Page 6: Introduction

    This manual describes the unit with an analog (0)4-20mA input type from the sensor "-A version". Other versions are available to process 0-10V sensor signals. One sensor with a passive or active (0)4-20mA signal output can be connected to the F074-A. To power the sensor, several options are available.
  • Page 7: Operational

    Page 7 2 OPERATIONAL GENERAL INFORMATION This chapter describes the daily use of the F074-A. This instruction is meant for users / operators. • The F074-A may only be operated by personnel who are authorized and trained by the operator of the facility. All instructions in this manual are to be observed •...
  • Page 8: Fig. 4: Example Of Display Information During Programming Lower Control Level

    • Control output The function of the F074-A, fill up or pump out, is determined at configuration level, not at Operator level. If the output signal is switched on, the text “CONTROL ON” is displayed. •...
  • Page 9: Configuration

    Make sure that the unit is not being used for any application when altering the settings. 3.2.1 ENTERING SETUP-LEVEL Configuration of the F074-A is done at SETUP-level, which can be reached at all times while the F074-A remains fully operational. At SETUP-level the display will deactivate the indicator and...
  • Page 10: Programming Sequence

    The combination of the SELECT-key and CLEAR-key is used to select a negative value. When a value can also be entered as a negative number, pressing the SELECT- key and CLEAR-key simultaneously will toggle the ‘–‘ (minus) sign on and off. FW-F074-A-M_v0404_01_EN.docx...
  • Page 11: Returning To Operator-Level

    Please keep a record of all settings for later reference. Use the control panel to return to OPERATE-level PROG-key In order to return to the operator level, press the PROG-key for three seconds. When no keys are pressed for 2 minutes, SETUP-level will be left automatically. FW-F074-A-M_v0404_01_EN.docx...
  • Page 12: Configuration Settings

    Page 12 CONFIGURATION SETTINGS All settings of the F074-A can be set via the control panel. The following paragraphs give a detailed description of each setting. 3.3.1 OVERVIEW FUNCTIONS SETUP LEVEL SETUP FUNCTIONS AND VARIABLES LEVEL UNIT L - m3 - kg - lb - GAL - USGAL - bbl - no unit...
  • Page 13: Explanation Of Setup-Menu 1 - Level

    Please note that the span (SETUP 2.3) has to be adapted as well; the calculation is not done automatically. DECIMALS This setting determines for height and its span the number of digits following the decimal point. The following can be selected: 00000 - 1111.1 - 222.22 FW-F074-A-M_v0404_01_EN.docx...
  • Page 14: Explanation Of Setup-Menu 3 - Control

    If a LED backlight has been supplied, it can be turned on or off. BL. BRIGHTNESS The backlight brightness is adjustable. The following can be selected: (optional) 1 – 5 (where 1 is minimum and 5 is maximum brightness) FW-F074-A-M_v0404_01_EN.docx...
  • Page 15: Explanation Of Setup-Menu 5 - Power Management

    When used with the internal battery option, the user can expect reliable measurement over a long period of time. The F074-A has several smart power management functions to extend the battery life time significantly. Two of these functions are available.
  • Page 16: Explanation Of Setup-Menu 7 - Others

    This protection is disabled with value 0000 (zero). Up to and including 4 digits can be programmed, for example 1234. TAGNUMBER For identification of the F074-A and communication purposes, a unique tag number of maximum 7 digits can be entered. FW-F074-A-M_v0404_01_EN.docx...
  • Page 17: Installation

    Operating Manual before carrying out its instructions. • The F074-A may only be operated by personnel who are authorized and trained by the operator of the facility. All instructions in this manual are to be observed.
  • Page 18: Handling The F-Series Enclosure

    The F0-Series can be supplied as suitable for Safe Area or Hazardous Area. Suitability for Intrinsic Safety is indicated in the model code by Type XI (e.g. F074-A-XI). For Intrinsically Safe applications: Installation and identification labels are shown in chapter 5.
  • Page 19: Fig. 9: Identification - Example Of F0-Series Installation Label (Safe Area - Type Pm Or Pf)

    The serial number can be reviewed on the identification label or in SETUP-menu Others. The production date is either shown separately on the label or indicated by the first 4 digits of the serial number representing year and week number (YYWW). FW-F074-A-M_v0404_01_EN.docx...
  • Page 20: Opening / Removing The Cover

    Plastic enclosure: 1 Nm per screw Aluminum enclosure: 1 Nm per screw Aluminum w. extended back enclosure: 1 Nm per screw Stainless steel enclosure: 2 Nm per screw 5. The F-Series in now ready to be returned to service. FW-F074-A-M_v0404_01_EN.docx...
  • Page 21: Mechanical Installation

    0.12" 0.12" M20 x 1,5 3x 1/2"NPT 25mm 25mm 15 15 M20 x 1,5 M20 x 1,5 4x M20 x 1,5 29.1 mm (1.15”) 115 mm (4.53”) 31 mm (1.22”) Fig. 10: Dimensions – Aluminum and stainless steel enclosures FW-F074-A-M_v0404_01_EN.docx...
  • Page 22: Dimensions - Non-Metallic Enclosures

    118 mm (4.65”) 25mm 25mm D=20mm D=20mm 12mm 12mm 30mm 30mm 24mm 24mm D=12mm D=16mm D=16mm D=20mm 36mm 36mm 0.12” 0.12” D=22mm (0.866") 3x D=22mm (0.866”) 29.1 mm (1.15”) 115 mm (4.53”) 31 mm (1.22”) Fig. 11: Dimensions – Non-metallic enclosures FW-F074-A-M_v0404_01_EN.docx...
  • Page 23: Mounting

    Meter mount by using one of the openings Pipe mount by using the mounting plate in the bottom of the back cover. with the bracket and hose clamps (accessory). Panel mount by using only the front cover Fig. 12: Installation – Mounting configurations FW-F074-A-M_v0404_01_EN.docx...
  • Page 24: Electrical Installation

    General directions: • The F074-A that came with a power module type PM; 110V-230V AC or type PD/PF with an option OR (the relays can handle 110V-230V AC) shall be connected to the Protective Earth (PE) stud which is installed in the metal back panel.
  • Page 25: Field Wiring Connections

    Within the United States all field wiring must conform to the National Electric Code, NFPA 70, Article 501-4(b). All field wiring enters the F074-A through the bottom of the enclosure and connects to the circuit assembly inside the enclosure. Wiring is routed through cable glands. Please make sure to order the F074-A with the correct drilling pattern and thread (metal) or hole (plastic) sizes.
  • Page 26: Power Supply Wiring

    C22.2 No. 61010-1 / UL61010-1 / EN/IEC 61010-1. The F074-A can be powered from an external power supply. An internal power supply is also available in the form of a lithium battery. When both external and internal power supplies are available, the internal power supply is interrupted and will act as a backup supply.
  • Page 27: Terminal Connectors Safe Area Applications - Type Pb / Pd / Pl / Px

    4.6.1 TERMINALS 1-2: SENSOR INPUT The F074-A requires a (0)4-20mA sensor signal which will be processed 4 times a second with a 16 bits accuracy. The input is not isolated. The screen of the signal wire can be connected to the common ground terminal. See paragraph 4.5.3.
  • Page 28: Terminal 4-5: Power Supply - Type Px (Default) And Pd (Option)

    TERMINAL 4-5: POWER SUPPLY - TYPE PX (DEFAULT) AND PD (OPTION) To power the F074-A an internal battery can be used (type PB) and / or an external DC power supply of 8-30V DC (type PX) or 16-30V DC (type PD). Connect the "-" to terminal 4 and the "+" to terminal 5.
  • Page 29: Terminal Gnd-1-2: Power Supply

    Page 29 4.7.1 TERMINAL GND-1-2: POWER SUPPLY To power the F074-A with a power supply option of type PF or type PM, connect a suitable power supply to the terminals as indicated in below table: Terminal Power supply Power supply option 24V AC ...
  • Page 30: Terminals 5-7: Sensor Input

    4.7.3 TERMINALS 5-7: SENSOR INPUT The F074-A requires a (0)4-20mA sensor signal which will be processed 4 times a second with a 16 bit accuracy. The input is not isolated. The screen of the signal wire can be connected to the common ground terminal. See paragraph 4.5.3.
  • Page 31: Intrinsically Safe Applications

    The F0-Series can be supplied as suitable for Safe Area or Hazardous Area. Suitability for Intrinsic Safety is indicated in the model code by Type XI (e.g. F074-A-XI). If Type XI is not indicated your device is not suitable for Intrinsically Safe applications!
  • Page 32: Electrical Installation In Hazardous Area

    Ga, the indicator shall be installed so, that even in the event of rare incidents, an ignition source due to impact or friction sparks between the enclosure and iron/steel is excluded. FW-F074-A-M_v0404_01_EN.docx...
  • Page 33: Electrical Data - Control Drawing

     The cable parameters are determined by the parameters of the system into which the F0-Series General Purpose Indicators is connected.  Only certified Intrinsically Safe Fluidwell battery type FW-LiBat-0xx may be used and replaced in hazardous area. The entity parameters for F0-Series General Purpose Indicators, model F0xx-A-XI, are as follows: Terminals 1 and 2 –...
  • Page 34  The cable parameters are determined by the parameters of the system into which the F0-Series General Purpose Indicators is connected.  Only certified Intrinsically Safe Fluidwell battery type FW-LiBat-0xx may be used and replaced in hazardous area. The entity parameters for F0-Series General Purpose Indicators, model F0xx-A-PL-XI, are as follows: Terminals 1 and 2 –...
  • Page 35: Installations Based On Atex Or Iecex Certificate

    Ga, the indicator shall be installed so, that even in the event of rare incidents, an ignition source due to impact or friction sparks between the enclosure and iron/steel is excluded. • For EPL Da the ambient temperature Ta shall not exceed 50 °C. FW-F074-A-M_v0404_01_EN.docx...
  • Page 36: Electrical Data - Annex 1

    (terminals 11 and 12) 30 V 0 mH 100 mA 6.1 nF = 0.75 W From the safety point of view the circuits shall be considered to be connected to earth. FW-F074-A-M_v0404_01_EN.docx...
  • Page 37: Terminal Connectors Intrinsically Safe Applications

    5.3.1 POWER SUPPLY WIRING The F074-A can be powered from an external power supply. An internal power supply is also available in the form of a lithium battery. When both external and internal power supplies are available, the internal power supply is interrupted and will act as a backup supply. Note that the optional backlight only works with an external power supply.
  • Page 38: Configuration Examples Intrinsically Safe Applications

    Please note: Type PX may be used in combination with the battery (Type PC). PX will power the F074-A, the battery will be disabled automatically until the power is disconnected. Configuration example IIA - IIB and IIC application - F074-A-OT-PD-XI-ZB 5.4.2...
  • Page 39: F074-A-Ot-Pl-Xi-Zb - Ex Ia Iic/Iiic

    Fig. 29: F074-A-OT-PL-XI-ZB - Ex ia IIC/IIIC - Intrinsically Safe application. Sensor supply voltage not available in this example. Please note: Type PL may be used in combination with the battery (Type PC). PL will power the F074-A, the battery will be disabled automatically until the power is disconnected. FW-F074-A-M_v0404_01_EN.docx...
  • Page 40: Maintenance

    (above 90% annual mean). It is the users responsibility to take all precautions to dehumidify the internal atmosphere of the F074-A in such a way that no condensation will occur, for example by placing dry silica-gel sachet in the casing just before closing it.
  • Page 41: Battery Replacement

    Safe area applications – Type PB • Before replacing the battery, verify that the new battery is undamaged, in good condition and suitable for use in the unit. (Type: StdLiBAT021 - re-ordering nr. SPB02) Fig. 31: Marking Type PB battery: Safe area StdLiBAT021 (SPB02) FW-F074-A-M_v0404_01_EN.docx...
  • Page 42: Replace The Battery

    Dispose of batteries in accordance with the (inter)national, the manufacturer’s and the plant owner’s standards and regulations. • Batteries pose an environmental hazard. • Do not dispose of as general waste or incinerate. • Return used batteries to a recycling point. FW-F074-A-M_v0404_01_EN.docx...
  • Page 43: Technical Specification

    Type HJ Drilling: 3x 22mm (0.87”). Type HK Flat bottom - no drilling. Operating temperature Safe area -40°C to +80°C (-40°F to +178°F). Intrinsically Safe -40°C to +70°C (-40°F to +158°F). For EPL Da: -40°C to +50°C (-40°F to +122°F) FW-F074-A-M_v0404_01_EN.docx...
  • Page 44 ANSI/UL 60079-0 FM Class 3610 ANSI/UL 60079-11 FM Class 3810 RoHS EN 50581 IEC 63000 IP & NEMA EN 60529 ANSI/IEC 60529 NEMA 250 Note: See the applicable Declaration of Conformity or product certificate for specific revisions and publication dates. FW-F074-A-M_v0404_01_EN.docx...
  • Page 45 Decimals 0 - 2 Percentage Digits 3 digits. Decimals Control values Digits 6 digits. Unit According to Level Decimals According to Level Type of control low and high level control. Includes delay time and configurable fill-up / pump-out functionality FW-F074-A-M_v0404_01_EN.docx...
  • Page 46: Problem Solving

    Page 46 PROBLEM SOLVING In this appendix, several problems are included that can occur when the F074-A is going to be installed or while it is in operation. Level displays "0 / zero" while a signal is available: Check: • SETUP 1.3 / 2.3: is the span correct? •...
  • Page 47: Declaration Of Conformity

    Last two digits of the year in which the U CA marking was affixed: 22. I. Mei , Manager Technology . .Bo 6 5 60 AA e hel he etherlands oltawe 5 66 A e hel he etherlands luidwell B is 001 certified b A ertification B eander 1051 6 Arnhem he etherlands. FW-F074-A-M_v0404_01_EN.docx...
  • Page 48: Index Of This Manual

    7, 9, 17, 31, 40 display update time operator level functional description pass code Height power supply decimals range error 8, 46 measuring unit sensor supply voltage span SETUP-level high current signal input input signal terminal connectors 27, 28 FW-F074-A-M_v0404_01_EN.docx...
  • Page 49: List Of Figures

    Fig. 13: Protective Earth (PE) connections on metal enclosure Fig. 14: Switch position voltage selection (type PF and PM). Fig. 15: Overview of terminal connectors F074-A – type PB / PD / PL / PX Fig. 16: Terminal connections - Analog signal input.
  • Page 50 Page 50 FW-F074-A-M_v0404_01_EN.docx...
  • Page 51 Page 51 FW-F074-A-M_v0404_01_EN.docx...
  • Page 52 _ _ _ _ _ _ _ 7.4 pass code 0000 7.5 tagnumber 0000000 Fluidwell bv PO box 6 Voltaweg 23 Website: www.fluidwell.com 5460 AA Veghel 5466 AZ Veghel Find your nearest representative: www.fluidwell.com/representatives The Netherlands The Netherlands Fluidwell bv - © 2022 - FW-F074-A-M_v0404_01_EN.docx FW-F074-A-M_v0404_01_EN.docx...