Properties
Electrical isolation
Permissible potential difference (to mounting rail)
Insulation tested with
Current consumption from rated supply voltage
(1L+)
Power loss of the module
Interrupts
Diagnostics function
Updating the firmware of the IM151-1 STANDARD
The IM151-1 STANDARD firmware can be updated starting with
accessible nodes).
To update the firmware, you receive files (*.UPD) with the current firmware.
The following requirements must be met:
● The IM151-1 STANDARD in the station whose firmware is to be updated must be
accessible online.
● The files with the current firmware version must be available in the file system of your
programming device or PC.
You can find information on this procedure in the
Note
Make sure that the correct firmware version for the interface module in question is used for
the update. An interface module with an older order number cannot be updated with the
firmware version for an interface module with a more recent order number and vice versa.
10
Reverse polarity protection
Voltage failure backup
Between backplane bus and electronics
Between PROFIBUS DP and electronics
Between supply voltage and electronics
Group error
PROFIBUS DP bus monitoring
Monitoring of the power supply voltage of the
electronics
Dimensions and weight
Yes
Min. 20 ms
No
Yes
No
75 V DC / 60 V AC
500 V DC
Approx. 200 mA
Typically 3.3 W
Status, interrupts, diagnostics
Yes
Yes
Red "SF" LED
Red "BF" LED
Green "ON" LED
STEP 7
Interface module IM151-1 STANDARD (6ES7151-1AA06-0AB0)
STEP 7
V5.1, SP 3 (via
online help.
Manual, 07/2015, A5E01075950-AD