IST-2138.EC01.01/C
Tabella 11 / Table 11 / Tableau 11
"S1-SET"
(Dip-Switch)
Alarm levels(Relays) / Niveaux d'alarmes(Relais)
1
2
3
ALARM 1
OFF
OFF
OFF
5,0 ppm
ON
OFF
OFF
3,5 ppm
OFF
ON
OFF
7,5 ppm
ON
ON
OFF
5,0 ppm
OFF
OFF
ON
TLV-TWA
3.0 ppm
ON
OFF
ON
OFF
ON
ON
ON
ON
ON
COSHH = Ente Europeo / European Department / Organisme européen
Imbocco Femmina ¾" Gas Conico UNI 6125
"¾" UNI 6125 Female Gas Conical Thread
Entrée femelle ¾" Gaz Conique UNI 6125
105
70
107
Ø42
Fig. 1 – Dimensioni / Size / Dimensions
Fig. 3 - Tester di calibrazione
/ Calibration Tester / Kit de Calibration
TECNOCONTROL S.r.l. - Via Miglioli, 47 20090 SEGRATE (MI) ITALY
Istruzione / User's Manual / Manuel d'utilisation
SE138EN2 (
Biossido di azoto / Dioxyde d'azote / Dioxyde d'azote
Livelli Allarme (Relé)
ALARM 2
10,0 ppm
7,5 ppm
10,0 ppm
7,5 ppm
(OSHA)
(OSHA)
TLV-STEL C
5.0 ppm
Risevato / Reserved / Réservé
Risevato / Reserved / Réservé
Risevato / Reserved / Réservé
83
190
65
1 L/min
0,3 L/ min
Relays Delay (Seconds) / retarde du relais (Secondes)
ALARM 3
ALARM 1
15,0 ppm
12
15,0 ppm
12
15,0 ppm
12
12,5 ppm
12
(OSHA)
TLV- C
0
15.0 ppm
OSHA = Ente Americano / U.S. Department / Organisme Etats-unien
Centrale rivelazione gas
Gas Central Unit
Centrale de détection
RL
-
+
Uscita in 4÷20 mA
4÷20 mA Output
Sortie en 4÷20 mA
S
-
12÷24Vdc
Alimentazione
Power Supply
+
Alimentation
Fig. 2 - Schema di collegamento / Wiring diagram / Schéma
RL
Ohm
800
RL=Resistenza di carico / Load resistor / Resistance de charge
Area di funzionamento
700
Allowable oparating region
650
600
500
400
350
300
200
100
50
0
0
5
Alimentazione / Power Supply / Alimentation
Fig.4 - Alimentazione / Resistenza di Carico 4÷20mA
Power supply / Load resistance diagram 4÷20mA
Alimentation / Résistance de charge 4÷20mA
Tel. +39 02 26922890 - Fax +39 02 2133734
)
Ritardo dei Relé (in Secondi)
ALARM 2
ALARM 3
30
60
30
60
30
60
30
60
0
0
Risevato / Reserved / Réservé
Risevato / Reserved / Réservé
Risevato / Reserved / Réservé
Dip Switch
Scheda Uscite Relé
1 2 3 4
Relays Output Board
Sortie sur Realis
F1
F2
TP1 TP2
10
15
20
10,8
Pag.18/18
FAULT
30
30
30
30
30
ON
SET
OFF
Test Uscita
Output Test
Sortie Test
40÷200mV
mV
25
28
24
Vdc