32
Target pressure adjusting
Mode setting method
Service unit PCB DIP switch on : No.5
Select the mode using '▶', '◀' Button :
"Func" Push the '●' button
Select the Function using '▶', '◀' Button :
"Fn8" Push the '●' button
Select the Option using '▶', '◀' Button :
"HEAT" , "COOL" Push the '●' button
Select the Option using '▶', '◀' Button :
"oFF ", " op1 " ~ "op7 " Push the '●' button
Target pressure is set
Setting
Mode
Low Pressure (kpa)
oFF
804
op1
699
op2
739
op3
843
op4
908
op5
961
op6
1026
op7
804
!
CAUTION
• Ask an authorized technician to setting a function.
• If do not use a function, set an off-mode.
• Change a power consumption or capacity.
High pressure (kpa)
2990
3121
2827
2696
2565
2435
2304
2990