Night Low Noise Function

In cooling mode, this function makes the ODU fan operate at low RPM
to reduce the fan noise of ODU at night which has low cooling load.
Night low noise function setting method
Master unit PCB DIP switch on : No.5
Select the mode using '▶', '◀' Button :
"Func" Push the '●' button
Select the Function using '▶', '◀' Button :
"Fn3" Push the '●' button
Select the Option using '▶', '◀' Button :
"oP1~oP15" Push the '●' button
Start the Night low noise function :
Save the selected option value in EEPROM
Time Settings
Step
Judgement Time(Hr)
oP1
8
oP2
6.5
oP3
5
oP4
8
oP5
6.5
oP6
5
oP7
8
oP8
6.5
oP9
5
oP10
oP11
oP12
oP13
6.5
oP14
6.5
oP15
6.5
CAUTION
!
• Request installer to set the function during installation.
• If ODU RPM changes, cooling capacity may go down.

Setting the ODU address

Mode setting method
Master unit PCB DIP switch on : No.5
Select the mode using '▶', '◀' Button :
"Func" Push the '●' button
Select the Function using '▶', '◀' Button :
"Fn5" Push the '●' button
Select the Option using '▶', '◀' Button :
"0" ~ "254" Push the '●' button
ODU address is set
CAUTION
!
• Ask an authorized technician to setting a function.
• If use a function, first install a Central controller.
Operation Time(Hr)
9
10.5
12
9
10.5
12
9
10.5
12
continuous operation
continuous operation
continuous operation
10.5
10.5
10.5
Snow removal & rapid defrost
Mode setting method
Master unit PCB DIP switch on : No.5
Select the mode using '▶', '◀' Button :
"Func" Push the '●' button
Select the Function using '▶', '◀' Button :
"Fn6" Push the '●' button
Select the Option using '▶', '◀' Button :
"oFF","oP1" ~ "oP3" Push the '●' button
Mode is set
Mode setting
setting
oFF
oP1
oP2
oP3
Snow removal mode. + Rapid defrost mode.
CAUTION
!
• Ask an authorized technician to setting a function.
• If do not use a function, set an off-mode.

Target pressure adjusting

Mode setting method
Master unit PCB DIP switch on : No.5
Select the mode using '▶', '◀' Button :
"Func" Push the '●' button
Select the Function using '▶', '◀' Button :
"Fn8" Push the '●' button
Select the Option using '▶', '◀' Button :
"hEAt" , "cooL" Push the '●' button
Select the Option using '▶', '◀' Button :
"oFF", "oP1" ~ "oP4" Push the '●' button
Target pressure is set
Setting
Mode
Cool
Setting
Low pressure
oFF
778 kPa
oP1
699 kPa
oP2
739 kPa
oP3
843 kPa
oP4
908 kPa
oP5
961 kPa
oP6
1 026 kPa
CAUTION
!
• Ask an authorized technician to setting a function.
• If do not use a function, set an off-mode.
• Change a power consumption or capacity.
Mode
Not setting
Snow removal mode
Rapid defrost mode
Heat
High pressure
2 990 kPa
3 121 kPa
2 827 kPa
2 696 kPa
2 565 kPa
2 435 kPa
2 304 kPa