Target Pressure Adjusting - LG MULTI V JRUN120LTE5 Installation Manual

Table of Contents

Advertisement

ELECTRICAL WIRING
74

Target pressure adjusting

Mode setting method
Setting
mode
"Heat"
oFF
Not setting
op1
Increase capacity
op2
Decrease power consumption
op3
Decrease power consumption Decrease power consumption
op4
Decrease power consumption Decrease power consumption
op5
Decrease power consumption Decrease power consumption
op6
Decrease power consumption Decrease power consumption
CAUTION
!
• Ask an authorized technician to setting a function.
• If do not use a function, set an off-mode.
• Change a power consumption or capacity.
Master unit PCB DIP switch on : No.5
Select the mode using ' ', ' ' Button :
"Func" Push the '●' button
Select the Function using ' ', ' ' Button :
"Fn8" Push the '●' button
Select the Option using ' ', ' ' Button :
"HEAT" , "COOL" Push the '●' button
Select the Option using ' ', ' ' Button :
"op1" ~ "op6" Push the '●' button
Target pressure is set
Purpose
"Cool"
Increase capacity
Increase capacity
Condensing
Evaporating
temperature
temperature
variation
variation
+2 °C
-3 °C
-2.5 °C
-1.5 °C
-4.5 °C
+2.5 °C
-6.5 °C
+4.5 °C
-8.5 °C
+6.5 °C
-10.5 °C
+8.5 °C